Chapter 3 Installation 27
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
3.8 Installing SmartCabniet Monitoring System
See Table 3-7 for the configuration of the SmartCabniet monitoring system.
Table 3-7 Configuration of the SmartCabniet monitoring system
No.
Product name
Quantity
Product external model
1
MSC intelligent monitoring card
1
MSC-C-C
2
Intelligent tmperature sensor
2
IRM-S01T
3
Water leakage detective belt sensor
1
IRM-S01W (5m)
4
Wireless Modem (USB port, optional)
1
TD-8311 USB 3G modem
5
Intelligent digital input sensor with RJ45 ports
1
IRM-S04DIF
Installing MSC intelligent monitoring card
The MSC intelligent monitoring card is a Web/SNMP intelligent device monitoring card, which can monitor the system
state of intelligent devices, record alarm events, and notify the user of the intelligent device alarms through email or
SMS mode. The MSC intelligent monitoring card also enables you to set operating parameters and view device
states through the embedded Web HMI, moreover, it can send the states of the monitored intelligent devices to the
network management software (NMS) through SNMP protocol mode.
The appearance of the MSC-C card is shown in Figure 3-21.
Figure 3-21 Appearance of the MSC intelligent monitoring card
Table 3-8 Performance specifications
Connected component
Cable standard
Connected distance (unit: m)
Connected number /
connected point
Port connecting to node
Twisted pair cable of
standard category 4
≤ 100
8*
Note*: The intelligent devices all connect to COM2 of MSC intelligent monitoring card, and the device number in serial
connection cannot exceed 8pcs
Notes
When installing MSC intelligent monitoring card, take the following precautions to avoid personnel injury and device
damage by accident.
Always cut off the power before performing any installation operation on the MSC intelligent monitoring card
Ensure that the external devices are connected to the correct MSC intelligent monitoring card ports
Wear an ESD wrist-wrap during installation
Arrange the wires properly, and do not put any heavy objects on the wires or stamp the wires
Make sure that the jumpers of MSC intelligent monitoring card are set to correct position. The jumper locations are
shown in Figure 3-22. See Table 3-9 for the jumper setting of the MSC intelligent monitoring card.