16 Chapter 3 Installation
SmartCabinet Series Solution Product for IDC or Computer Rooms User Manual
3.2 Installing Air Conditioner of 600mm Wide Standard Unit
The AC components comprise AC indoor unit, and AC outdoor unit. When delivery, the AC indoor unit has been
installed in the cabinet before delivery, the AC outdoor unit is placed inside the cabinet and delivered with the cabinet.
In field, you need to place the AC outdoor unit reasonably, connect copper pipes between the AC indoor unit and
outdoor unit, vacuum and connect cables.
Removing And Placing Outdoor Unit
1. Remove the four screws on the press strips of outdoor unit, and remove the two press strips, as shown in
Figure 3-3.
Figure 3-3 Removing the press strips of outdoor unit
2. Remove the four screws on the four corners of outdoor unit, and carry the AC outdoor unit out, as shown in
Figure 3-4.
Figure 3-4 Removing the fixing screws of outdoor unit
Note
1. In Figure 3-3, the two metal press strips on top of the outdoor unit can be used as horizontal cable organizers at back end of the
cabinet.
2. In Figure 3-4, the two 1U-height supporting part of AC outdoor unit at lower part of the outdoor unit can be used as dummy
plates in cold aisle of the cabinet.
A
A amplified
Press strip (2 pcs)
Screw (4 pcs)
AC outdoor unit
A
A amplified
Screw (4 pcs)
AC outdoor unit
Supporting part of AC
outdoor unit (2 pcs)