Power MoNITorING

INSTALLATIoN GUIDe

E30

Installer’s Specifications

Inputs:

   Input Power 

90-277VAC, 50/60 Hz

Accuracy:

   Power/Energy 

IEC 62053-21 Class 1, ANSI C12.1-2008

   Voltage 

±0.5% of reading 90-277V line-to-neutral   

Operation:

   Sampling Frequency 

2560 Hz

   Update Rate 

1.8 seconds (both panels)

   Overload Capability 

22 kAIC

Outputs:

   Type 

Modbus RTU

   Connection 

DIP switch-selectable 2-wire or 4-wire, RS-485

   Address 

DIP switch-selectable address 1 to 247 (in pairs of 2)*

   Baud Rate 

DIP switch-selectable 9600, 19200, 38400

   Parity 

DIP switch-selectable NONE, ODD, EVEN

   Communication Format 

8-data-bits, 1-start-bit, 1-stop-bit

   Termination 

5-position depluggable connector 

    

(TX+ TX- SHIELD TX+/RX+ TX-/RX-)

Mechanical:

   Ribbon Cable Support 

4 ft. (0.9 m) flat ribbon cable ships standard; 

    up 

to 20 ft. (6 m) available

Environmental:

   Operating Temperature Range 

0° to 60°C (32° to 140°F) (<95% RH noncondensing)

   Storage Temperature Range 

-40° to 70°C (-40° to 158°F)

   Altitude of Operation 

3000 m

Agency Approvals 

UL508, EN61010

* See Configuration section for details.

Panelboard Monitoring System

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  Follow safe electrical work practices. 

See NFPA 70E in the USA, or applicable local codes.

•  This equipment must only be installed and serviced by qualified electrical personnel.
•  Read, understand and follow the instructions before installing this product.
•  Turn off all power supplying equipment before working on or inside the equipment.
•  Use a properly rated voltage sensing device to confirm power is off.
  DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
•  Only install this product on insulated conductors.

Failure to follow these instructions will result in death or serious injury.

DANGER

NOTICE

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  The installer is responsible for conformance to all applicable codes.

•  Mount this product inside a suitable fire and electrical enclosure.

FCC PART 15 INFORMATION
NOTE:  This equipment has been tested by the manufacturer and found 

to comply with the limits for a class A digital device, pursuant to part 
15 of the FCC Rules. These limits are designed to provide reasonable 
protection against harmful interference when the equipment is 
operated in a commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if not installed and 
used in accordance with the instruction manual, may cause harmful 
interference to radio communications. Operation of this equipment in 
a residential area is likely to cause harmful interference in which case 
the user will be required to correct the interference at his own expense. 
Modifications to this product without the express authorization of 
Veris Industries nullify this statement. 

Product IdentIfIcatIon

E30

E30

CT Option

*Each strip contains 21 current sensors.

0 = 100A, 3/4" spacing
1 = 100A, 1" spacing

Description

A = Advanced
B =  Intermediate
C =  Basic

# of CTs

42 = 2 strips*
84 = 4 strips*

table of contents

Quick Install

2

Operation

2

Dimensions

2

Product Diagram

3

Data Output

3

Blink Codes for Status LED

3

Solid-Core CT Accuracy

3

Installation

4

Wiring

7

Configuration

8

Default DIP Switch Settings

8

Address Setup

9

Commissioning

10

Recommended Accessories

10

Safety

10

Troubleshooting

11

China RoHS Compliance Information IEFUP Table)

11

Summary of Contents for E30 series

Page 1: ...se a properly rated voltage sensing device to con rm power is o DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION Only install this product on insulated conductors Failure to follow these instructi...

Page 2: ...h circuits The E30B measures both current and power for the mains and current only in each circuit The E30C measures current only for the mains and branch circuits dimensions CircuitBoardandMountingBr...

Page 3: ...ors on the left are for panelboard 1 the two on the right are for panelboard 2 Note Connect CT strips to the correct ribbon cable connectors for each panel The top connector is for Strip A and the bot...

Page 4: ...20 20 20 20 20 20 20 20 A B A B A B A B Panel 1 Panel 2 1 5 9 13 17 21 25 29 33 37 41 3 7 11 15 19 23 27 31 35 39 2 6 10 14 18 22 26 30 34 38 42 4 8 12 16 20 24 28 32 36 40 A B A B 1 5 9 13 17 21 25 2...

Page 5: ...on 5 Install the E30 acquisition board mounting bracket in the panel using screws and bolts provided Figure 3 A grounding connection is located on the mounting bracket near the lower right corner Use...

Page 6: ...p I1 I2 I3 IN I1 I2 I3 IN Panel2 Panel1 CTInput 0 0 333VAC CTInput 0 0 333VAC E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP E30 CURRENT SENSOR STRIP Panel1 Panel2 Recommen...

Page 7: ...Wire 4 Wire 2 WireExample Figure11 Belden1120Aor equivalent 120 terminator onlastdeviceof daisychain NotUsed WARNING After wiring the RS 485 cable remove all scraps of wire or foil shield from the ele...

Page 8: ...RS 485 2 Address Configuration Each Modbus device on a single network must have a unique address Set the switch block to assign a unique address before the device is connected to the Modbus RS 485 ne...

Page 9: ...andtheVeris V logoaretrademarksorregisteredtrademarksof VerisIndustries L L C intheUSAand orothercountries TM E30 INSTALLATION GUIDE Address Setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15...

Page 10: ...If Veris E30 products are used in installations with circuits higher than the product ratings the circuits must be kept segregated per UL508A Sec 17 5 Note 277 480 VAC Wye connected center grounded p...

Page 11: ...ng This can be caused by a signal greater than 100 A or 277V L N or by a signal with highTHD near the gain stage switching points 1 5 A and 10 A The main board has a flashing green light Everything is...

Reviews: