1.3
FIREPLACE / SURROUND SUITABILITY
The fire must only be installed on a hearth it
must not be installed directly onto
carpet or other combustible floor materials.
The fire is suitable for fitting to
non-combustible fire place surrounds and proprietary fire place surrounds with a
temperature rating of at least 150oc. (Class “O”)
If a heating appliance is fitted directly against a wall without the use of a fire
surround or fire place all combustible material must be removed from behind
the trim. Soft wall coverings such as blown vinyl, wall paper etc. could be
affected by the rising hot air and scorching and / or discoloration may result.
Due consideration should be made to this when installing or decorating.
1.4
SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum
distance of 200mm above the top of the fire and the shelf does not project more
than 150mm. If the shelf overhangs more than 150mm the distance between the
fire and the shelf must be increased by 15mm for every 25mm of additional
overhang over 150mm.
1.5
FLUE / CHIMNEY INSPECTION
Before commencing installation, a flue or chimney should be inspected to ensure
that all the following conditions are satisfied.
1.
Check that the chimney / flue only serves one fire place and is clear of any
obstruction. Any dampers or register plates must be removed or securely
locked in the open position.
2.
Brick / stone built chimneys or any chimney or flue which has been used
for an appliance burning fuel other than gas must be thoroughly swept.
The base of the chimney / flue must also be thoroughly cleared of debris
etc.
3.
Any under-floor air supply to the fire place must be completely sealed off.
4.
Ensure that the inside of the chimney / flue is in good condition along it’s
length and check that there is no leakage of smoke through the structure
of the chimney during and after the smoke pellet test.
5.
Using a smoke pellet, check that there is an up-draught in the
chimney / flue and that the smoke can be seen issuing from the
terminal / chimney pot outside.
There must be no leakage of smoke through the structure of
the chimney during or after the smoke pellet test and it is
important to check inside upstairs rooms adjacent to the chimney /
flue
.
5