The day timer settings have higher priority as compared to the week timer.
If the day timer is activated the item "Operation mode" in the main window
will display the symbol "D".
To select the item to be edited (week day, on/off timer status for this day,
operation time in this mode, control temperature, fan speed) press Enter.
To edit the current value of the menu item use the Up/Down buttons.
Week operation programming example.
The required operation schedule for the air handling unit is as follows:
MONDAY
Set the room temperature 24 °C from 08:00 till 23:00 and set the medium speed
for the supply fan.
Set the room temperature 21 °C from 23:00 till 08:00 and set the minimum speed
for the supply fan.
TUESDAY
Set the room temperature 23 °C from 09:00 till 22:00 and set the maximum speed
for the supply fan.
Set the room temperature 20 °C from 22:00 till 09:00 set the room temperature 20 °C and
set the minimum speed for the supply fan.
WEDNESDAY
disable
THURSDAY
disable