1.0   Introduction

 

 

 

 

1.1 

Description 

(Fig. 1)

 

 

1. The HR200WJ unit is a through the wall heat 
recovery ventilator for use in kitchens and utility 
rooms. It is designed for installation in external 
walls having a thickness up to 335mm.

 

 

2. The unit’s twin impeller and heat exchanger 
arrangement simultaneously supplies and 
extracts air while transferring heat from the stale 
exhaust airflow to the fresh intake airflow. This 
provides up to 75% heat recovery from the stale 
extracted air.

 

 

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 

 

 
 

3. The power consumption for the unit is 9.5W 
trickle speed, 19.7W normal speed and 55W 
boost speed.

 

 

4. The three selectable speeds provide 
ventilation rates of 32m³/h trickle, 54m³/h normal 
and 104m³/h boost. 

 

 

 

1.2 

Ancillary Equipment

 

 

1. The HR200WJ unit can be used in conjunction 
with a range of ancillary equipment.

 

 

Controller:- 

see section

 

3.1 Controllers.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                                                                       4

Fig. 1

 

 

Summary of Contents for HR200WJ

Page 1: ...WJ Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR200WJ 47...

Page 2: ...should be provided with a local isolator switch fitted with a 3A fuse capable of disconnecting all poles and having a contact separation of at least 3mm 5 These units must be earthed 6 Precautions mu...

Page 3: ...and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be connected directly to a tumble drier 5 The supply...

Page 4: ...racts air while transferring heat from the stale exhaust airflow to the fresh intake airflow This provides up to 75 heat recovery from the stale extracted air 3 The power consumption for the unit is 9...

Page 5: ...Do not site the appliance in the vicinity of excessive levels of airborne oil or grease 7 If the unit is installed in a room containing a fuel burning appliance the installer must ensure that air rep...

Page 6: ...the cable runs WARNING Before deciding on the final position for the unit check there are no buried cables pipes or obstructions on the outside wall Cable requirements Suitably Basec or Har approved f...

Page 7: ...the top right hand side of the housing Note for the purpose of condensation drainage a prop is fitted to the underside of the housing to cause it to adopt a downwards tilt to the outside wall 4 Fix th...

Page 8: ...Connect the conductors of the cable to the appropriate terminals in accordance with the wiring diagram Fig 5 NOTE Refer to the fitting and wiring instructions provided with the controller used The wi...

Page 9: ...thoroughly CAUTION Keep water away from all electrical components and wiring within the unit 8 Reassemble in reverse order ensuring the filter and heat exchanger are seated correctly 9 Switch power s...

Page 10: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Page 11: ...mand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted...

Page 12: ...to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your...

Reviews: