3.0   Installation

 

 
 
 
 

 

 
 

 

 
 
 
 
 
 
 
 
 
 

 

 

3.3 

Installing the Appliance

 

 

From Inside 

1. Remove the grille, heat exchanger, from the 
unit. Note: it is not necessary to remove the 
fan assembly from the housing to carry out the 
installation.

 

 

2. Slide the unit into the mounting hole and 
ensure that the flange around its open end is not 
held off the mounting surface by the threaded 
bushes located in the flange. Remove the 
housing assembly and if necessary clear the wall 
to suit these bushes and the screws which will 
project through them.

 

 

 

 

 
 

 

 
 
 
 
 
 
 
 
 
 

3. Offer the housing to the mounting hole. As the 
housing is being located in the mounting hole, 
feed the electrical supply cable through the entry 
hole (located on the top right hand side of the 
housing). Note: for the purpose of condensation 
drainage a prop is fitted to the underside of the 
housing to cause it to adopt a downwards tilt to 
the outside wall.

 

 

4. Fix the housing assembly in the wall using suitable gap 
filler between it and the mounting hole. The housing can 
also be fixed to the wall through the holes in the side 
using suitable wood screws and wall plugs. Make good 
around the internal and external wall faces.

 

 

 

 

 

  

 

CAUTION: 

Ensure the case does not distort 

during fixing and making good.

 

 

 

 

 

 

From Outside

 

1. Offer the frame  to  the  housing  and mark  its 
fixing  hole  positions  on  the  external  wall  face. 
Remove  the  frame  and  drill  the  wall  to  accept 
suitable wall fixing plugs.

 

 

2. Slide the frame over the housing and seal it 
against the external wall face using silicone 
sealant or mastic. 

Fix it in position with suitable 

screws.

 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig. 4

 

 

Summary of Contents for HR200WJ

Page 1: ...WJ Through the wall Heat Recovery Ventilator Installation and Maintenance Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Stock Ref No HR200WJ 47...

Page 2: ...should be provided with a local isolator switch fitted with a 3A fuse capable of disconnecting all poles and having a contact separation of at least 3mm 5 These units must be earthed 6 Precautions mu...

Page 3: ...and maintenance 3 Certain applications may require the installation of sound attenuation to achieve the sound levels required 4 The unit must not be connected directly to a tumble drier 5 The supply...

Page 4: ...racts air while transferring heat from the stale exhaust airflow to the fresh intake airflow This provides up to 75 heat recovery from the stale extracted air 3 The power consumption for the unit is 9...

Page 5: ...Do not site the appliance in the vicinity of excessive levels of airborne oil or grease 7 If the unit is installed in a room containing a fuel burning appliance the installer must ensure that air rep...

Page 6: ...the cable runs WARNING Before deciding on the final position for the unit check there are no buried cables pipes or obstructions on the outside wall Cable requirements Suitably Basec or Har approved f...

Page 7: ...the top right hand side of the housing Note for the purpose of condensation drainage a prop is fitted to the underside of the housing to cause it to adopt a downwards tilt to the outside wall 4 Fix th...

Page 8: ...Connect the conductors of the cable to the appropriate terminals in accordance with the wiring diagram Fig 5 NOTE Refer to the fitting and wiring instructions provided with the controller used The wi...

Page 9: ...thoroughly CAUTION Keep water away from all electrical components and wiring within the unit 8 Reassemble in reverse order ensuring the filter and heat exchanger are seated correctly 9 Switch power s...

Page 10: ...4 months Clean cell replace filters the new filters will be supplied with 4 additional Timestrip indicators Note The above is the minimum requirement more frequent cleaning intervals may be needed dep...

Page 11: ...mand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers only Ext Leakage Rates for Ducted UVUs 5 Internal 5 External Mixing Rate of Non Ducted...

Page 12: ...to misuse neglect or damage Has not been modified or repaired by any person not authorised by the company IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your...

Reviews: