background image

Velbus manual VMB1RY– edition 1 – rev.1.0 

 

11

Operation: 
 

The relay module can be operated in different ways: 

  Using push buttons connected to the direct push button input: 

o

  activating the set mode on the module. 

  Using push buttons connected to the Velbus

®

 through a push button interface or control module: 

o

  switching on the relay. 

o

  switching off the relay. 

o

  switching the relay on or off. 

o

  activating the set mode on the module. 

o

  starting or stopping the timer. 

o

  starting or stopping the 2

nd

 timer. 

o

  starting or restarting the timer. 

o

  starting or restarting the 2

nd

 timer. 

 

LED indication: 

 

The control module LEDs and the operation mode LED on the relay module indicate the status of the relay: 

  The LED will not light if the relay is switched off. 

  The LED lights if the relay is switched on and the timer is not activated. 

  The LED blinks rapidly if the timer is activated. 

  The LED blinks slowly if the 2nd timer is activated.  

 
A short press will only be distinguished from a long press in the 2-way timer mode. A short press will activate the 
1st timer (TIME1) while a long press will activate the 2nd (TIME2) timer. 

 

Learning Mode: 

 

Only push buttons connected to the Velbus

®

 via a push button interface or a control panel are appropriate for the 

procedure below.  
Each command can accept up to 7 different push buttons.  
Memorize he unique address of the module. 
Set the module address on: 

 

Address 

Command 

F1 

OFF: Learning push buttons switching off the relay 

E1 

ON: Learning push buttons switching on the relay 

D1 

TGL: Learning push buttons switching the relay on or off 

C1 

PBM: Learning push buttons activating the set mode on the module 

B1 

TG1: Learning push buttons starting or stopping the timer 

A1 

TG2: Learning push buttons starting or stopping the 2nd timer  

91 

ST1: Learning push buttons starting or restarting the timer 

81 

ST2: Learning push buttons starting or restarting the 2

nd

 timer  

 
The relay will be switched off and the operation mode LED will blink very rapidly to indicate the learning mode. 
The indication LEDs of the learned push buttons will also blink very rapidly. In this way it is possible to see which 
push buttons for the corresponding group have already been learned. 
You can add a specific push button by maintaining it pressed until the relay switches on. When releasing the push 
button the relay will switch off and the push button indication LED will blink very rapidly as a confirmation. If this 
does not work then the maximum amount of push buttons has been reached. 
To delete a learned push button, maintain it pressed. When releasing the push button the indication LED will be 
turned off. 
You can delete all learned push buttons for a specific control group by maintaining the manual control on the relay 
module pressed until the relay switches on. When releasing the manual control push button the relay and the 
indication LEDs of all corresponding push buttons will turn off. 
Repeat the procedure above to learn other commands to the push buttons. 
Quit the learning mode by resetting the relay module’s original address. 
When using firmware version 0736 you will be able to delete all push buttons saved into the memory of the relay 
module at once. Set the address to one of the learning addresses. Maintain the manual control on the relay 
module pressed for 10 seconds. The relay will activate and deactivate again after 7 seconds to confirm the push 
buttons have been erased. Set the address back to its original value. 

 

Summary of Contents for Velbus VMB1RY

Page 1: ...Velbus manual VMB1RY edition 1 rev 1 0 1 VMB1RY Relay Module for VELBUS system ...

Page 2: ... 4 Connection 5 Direct control with several push buttons 6 Control via VELBUS system 6 Combination of direct push button control and VELBUS control 7 Use 8 Termination 8 Addressing 9 Timer setting 9 Operation mode timer2 9 Operation 11 LED indication 11 Learning mode 11 ...

Page 3: ...30min 1h 2h 5h 1day on off Controllable by connecting several push buttons in parallel Push button input debounce 65ms Control through VELBUS Programmable without PC Easy learning process by controlling the push buttons in the learning mode 8 different control possibilities Using push buttons turning on the relay Using push buttons turning off the relay Using push buttons turning the relay on or o...

Page 4: ...ich can be saved in the non volatile memory The module can react to push button messages sent over the VELBUS A modification of the relay status will be reported on the VELBUS When modifying the relay status the module will send instructions to adjust the status of the leds on the control modules Instructions will be accepted when calling up the module type module name module status reading from o...

Page 5: ...ugh a 4 pole relay L H PB BUS VMB1RY 12V NO NC COM COM N L AC POWER MODE TIME1 TIME2 ADDR A1 A2 1 3 2 4 LOAD 1 3 2 4 A1 A2 L H PB BUS VMB1RY 12V NO NC COM COM N L1 AC POWER MODE TIME1 TIME2 ADDR A1 A2 3 5 4 6 1 3 2 4 A1 A2 LOAD 6 5 8 7 1 2 7 8 L2 L3 N L1 L2 L3 Connect the 12 18VCC mind the polarity to the module Make sure to use a heavier wire gauge 1mm with long connections You can use the relay ...

Page 6: ... set the address on 00 so no status modifications will be reported All learned push buttons must be deleted see learning mode so no instructions will be sent over the VELBUS to control the push button indication leds In the other case de relay module will cause a bus error with every status modification Remark For connection between the modules use twisted pair cable ex EIB 2x2x0 8mm2 UTP 8x0 51mm...

Page 7: ...Y BUS TWISTED PAIR 0 5mm 2 12V NO NC COM COM N L AC POWER MODE TIME1 TIME2 ADDR Remark For connection between the modules use twisted pair cable ex EIB 2x2x0 8mm2 UTP 8x0 51mm CAT5 or other Use minimum 0 5mm cable For long wiring 50m or if a lot of modules 10 are connected to one wire use 1mm cable Connect the bus mind the polarity to the module ...

Page 8: ...mper in all other cases L H PB BUS 12V NO NC COM COM MODE TIME1 TIME2 ADDR TERM VELBUS Direct push button control 12V supply Operation mode LED Manual control Termination Relay on indication LED Normal open contact Normal closed contact Forwarding LED Reception LED Power LED Address setting Control mode setting Time setting Remark If different cable wiring topologies tree star loop are used place ...

Page 9: ...witch off the relay 1 Staircase lighting timer Operating the push button will switch on the relay After the set time see TIME1 rotary switch has elapsed the relay will turns off Operating the push button when the relay is switched on will restart the timer 2 Non restartable timer Operating the push button will switch on the relay After the set time see TIME1 rotary switch has elapsed the relay tur...

Page 10: ...tch off the delay C 2 way timer time 2 2h A short press will switch on the relay during the set time see TIME1 rotary switch A long press will switch on the relay for 2 hours Operating the push button when the relay is on will immediately switch off the delay D 2 way timer time 2 5h A short press will switch on the relay during the set time see TIME1 rotary switch A long press will switch on the r...

Page 11: ...odule B1 TG1 Learning push buttons starting or stopping the timer A1 TG2 Learning push buttons starting or stopping the 2nd timer 91 ST1 Learning push buttons starting or restarting the timer 81 ST2 Learning push buttons starting or restarting the 2nd timer The relay will be switched off and the operation mode LED will blink very rapidly to indicate the learning mode The indication LEDs of the lea...

Page 12: ...Velbus manual VMB1RY edition 1 rev 1 0 12 ...

Reviews: