7 Transfer measured values and data to the cloud

VEGAPULS Air 23 • Autarkic device with measured value transmission via radio technology

64314-EN-230606

7  Transfer measured values and data to the 

cloud

7.1  Communication basics

To transmit the measured values and data to the cloud, the device 

requires access to mobile network or a LoRaWAN network at the in-

stallation site, depending on the version. If no corresponding network 

is available, a LoRaWAN gateway must be installed.

Note:

Ensure free access to the radio network. The device must not be 

covered by metal or even enclosed. This especially for the medium 

height of the housing.

Note:

Simultaneous operation of LTE-M or LTE-IoT and LoRaWAN is not 

supported.
The following measured values or data are transmitted:

• 

Distance from the medium surface (m)

• 

Electronic temperature (°C)

• 

Geographical position determined by GNSS (geographical coor-

dinates)

• 

Mounting position (angle °)

• 

Remaining life of Lithium cells (%)

• 

Device status

The transmission options are described below.

7.2  NB-IoT/LTE-M - VEGA Inventory System

With NB-IoT (Narrow band Internet of Things) and LTE-M (Long 

Term Evolution for Machines), the focus is on low data rates and high 

transmission ranges. Another focus is on penetrating propagation 

obstacles, such as buildings, for which the long-wave signal is well 

suited.

API

VEGA Inventory System

Customer

Customer Database

Fig. 15: Wireless measured value transmission via NB-IoT and LTE-M to the 

VEGA Inventory System

Data is sent via an eSIM card integrated in the sensor. This card 

sends the data via mobile network directly to the VEGA Inventory Sys-

tem. If no mobile network is available, a fallback to LoRa takes place 

automatically (see below).

Summary of Contents for VEGAPULS Air 23

Page 1: ...Operating Instructions Radar sensor for continuous level measurement in plastic vessels VEGAPULS Air 23 Autarkic device with measured value trans mission via radio technology Document ID 64314...

Page 2: ...structions 11 4 3 Mounting preparations 12 4 4 Installation procedure 13 4 5 Transportation lock after mounting 15 5 Setup the most important steps 16 6 Activate device functions 18 6 1 Activate 18 6...

Page 3: ...data 33 13 2 Radio networks LTE M and NB IoT 37 13 3 Radio networks LoRaWAN Data transmission 37 13 4 Dimensions 40 13 5 Industrial property rights 41 13 6 Licensing information for open source softwa...

Page 4: ...t page of this instruction refers to the Docu ment ID By entering the Document ID on www vega com you will reach the document download Information note tip This symbol indicates helpful additional inf...

Page 5: ...instrument complying with all prevailing regulations and directives The instrument must only be operated in a technically flawless and reliable condition The operator is responsi ble for the trouble...

Page 6: ...obile radio network or LoRaWan are defined by selecting the country of use It is absolutely essential to do this during the job specific device configuration Caution Operation of the device with a fal...

Page 7: ...rmation sheet PINs and Codes with Identifier for LoRaWAN network Device EUI Application EUI App Key The further scope of delivery encompasses Documentation Safety instructions for lithium metal cell I...

Page 8: ...le 1 Order number 2 Wireless signal outputs frequency bands 3 Device EUI LoRa 4 Technical data 5 QR code for device documentation 3 2 Principle of operation VEGAPULS Air 23 is a radar sensor for conti...

Page 9: ...reless measured value transmission via mobile radio The transmission or evaluation is carried out via an Asset Manage ment System e g VEGA Inventory System The device is supplied with energy by integr...

Page 10: ...be left closed and stored according to the orientation and storage markings on the outside Unless otherwise indicated the packages must be stored only under the following conditions Not in the open Dr...

Page 11: ...ng that all parts of the instrument ex posed to the process are suitable for the existing process conditions An activated device see chapter Activate device also carries out measurements in horizontal...

Page 12: ...ould be as flat as possible or slightly curved outwards Note Mounting positions or vessel ceilings with an inwardly curved surface are not suitable for fastening 4 3 Mounting preparations The intended...

Page 13: ...face 3 Mounting ring 4 Housing lid The glue surface bonds adhesively to the surface of the IBC container and reaches its final adhesive strength after approx 72 hours A cor rection of the sensor posit...

Page 14: ...e fit Note For optimum measurement ensure direct permanent contact be tween the bottom of the sensor and the surface of the IBC container The device version for ceiling mounting has mounting brackets...

Page 15: ...ing and work with special care 4 5 Transportation lock after mounting The adhesive joint and the flexible mounting of the device are only designed for stationary operation of the vessel Danger During...

Page 16: ...d via Apple App Store Goog le Play Store Baidu Store Via magnet Via smartphone VEGA Tools app or VEGA Inventory System app Move the supplied magnet along the line towards the housing lid AC TIV AT IO...

Page 17: ...sured value transmission via radio technology 64314 EN 230606 Web portal VEGA Inventory System app Menu item Adjustment lineariza tion Open assistant measuring range and transmission interval via VEGA...

Page 18: ...n of the device in the VEGA Inventory System is not possible but is carried out on site via smartphone or magnet Take this into account before deactivation By smartphone Proceed as follows for activat...

Page 19: ...TIV ATIO N M agnet 3 2 1 Fig 11 Activate sensor Magnet 1 Radar sensor 2 Contact surface for magnet 3 Magnet Setup is now complete and the unit is ready for operation Note Devices for ceiling mounting...

Page 20: ...e successful activation with the message The sensor was activated serial no device VEGAPULS Air 23 Setup is now complete and the unit is ready for operation Via magnet Proceed as follows for activatio...

Page 21: ...the unit is ready for operation 6 2 Measurement function After activation a single measurement is carried out and the cyclic measurement interval is started The sensor delivers the distance value fro...

Page 22: ...ver via navigation satellites 1 Note With the LoRa version of the device the function Location is not available With activated position determination a GPS position determination is performed once dur...

Page 23: ...data are transmitted Distance from the medium surface m Electronic temperature C Geographical position determined by GNSS geographical coor dinates Mounting position angle Remaining life of Lithium c...

Page 24: ...responding gateway is required for this This gateway picks up the data via LoRa from the sensors and transmits them via cellular radio to VEGA s own LoRa server VEGA Inventory System LoRa 10 15 km VEG...

Page 25: ...rk In this case the sensor must be made known in this network Customer Customer Database Fig 18 Wireless measured value transmission To do this the user creates the sensor in his interface with its id...

Page 26: ...ic device with measured value transmission via radio technology 64314 EN 230606 8 Set up measuring point via the VEGA Inventory System app First select the device you want to add to the VEGA Inventory...

Page 27: ...m 1 1 0 2 Current version of the VEGA Inventory Systems Available mobile connection via NB IoT LTE M Readable parameters IMEI 3 Modifiable parameters Measuring range begin measuring range end Measurin...

Page 28: ...oid this remove the device from the vessel before cleaning 10 2 Rectify faults The operator of the system is responsible for taking suitable meas ures to rectify faults The device offers maximum relia...

Page 29: ...as dangerous goods and with the note that the cells are to be changed 10 4 How to proceed if a repair is necessary You can find an instrument return form as well as detailed information about the pro...

Page 30: ...a risk of ignition due to a possibly damaged Lithium cell In this case the device must not be packed or transported any further 11 2 Dismounting steps mounting ring The following tools are required t...

Page 31: ...ose of in accordance with local regulations Tip If a mounting ring is to be used again the adhesive surface is avail able from VEGA as a spare part 11 3 Disposal Pass the instrument on to a specialise...

Page 32: ...has been tested and approved ac cording to the current edition of the applicable country specific norms or standards The confirmations as well as regulations for use can be found in the document Radi...

Page 33: ...n mounting ring with flexibly exchangeable holder EPDM Cover gasket Silicone Weight depending on the version Glue connection ceiling mounting approx 0 35 kg 0 772 lbs Ceiling mounting with magnets app...

Page 34: ...nded measuring range Characteristics and performance data Measuring frequency W band 80 GHz technology Measuring cycle time 5 s Measuring and transmission interval every 15 minutes every 24 hours conf...

Page 35: ...ss of Operation A Optional ADR Feature Supported Yes Activation OTAA Ambient conditions Ambient temperature 20 60 C 4 140 F Storage and transport temperature 20 80 C 4 176 F Mechanical environmental c...

Page 36: ...72 years 12 h 5 02 years 24 h 7 75 years Additional output parameter Electronics temperature Range 20 60 C 4 140 F Resolution 0 1 K Deviation 3 K Electrical protective measures Protection rating Glue...

Page 37: ...hown You can find further information of LoRaWAN on www lora alliance org Data stream byte order packet structure The data are transferred as a byte stream in packets Each packet is given an identifie...

Page 38: ...1 Software version Customer 1 Measurement transmission interval 7 Change counter 2 Scaling min 4 Scaling max 4 Device Name 19 Device Tag 19 Total 11 19 16 24 35 39 Packet structure for operation in t...

Page 39: ...11 10 11 10 NAMUR status NAMUR status Message NAMUR status 0 1 2 3 4 Meaning Good Function Check Maintenance request Out of speci fication Failure VEGA Device status VEGA Device status Message VEGA de...

Page 40: ...dio technology 64314 EN 230606 13 4 Dimensions 96 mm 3 78 110 mm 4 33 106 mm 4 17 1 4 0 m m 5 4 9 120 mm 4 72 50 5 mm 1 99 96 mm 3 78 46 mm 1 81 5 6 m m 0 2 2 8 6 mm 0 34 1 2 Fig 23 Dimensions VEGAPUL...

Page 41: ...llec tuelle Pour plus d informations on pourra se r f rer au site www vega com VEGA lineas de productos est n protegidas por los derechos en el campo de la propiedad indus trial Para mayor informaci n...

Page 42: ...42 Notes VEGAPULS Air 23 Autarkic device with measured value transmission via radio technology 64314 EN 230606...

Page 43: ...43 Notes VEGAPULS Air 23 Autarkic device with measured value transmission via radio technology 64314 EN 230606...

Page 44: ...ing scope of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change withou...

Reviews: