47
13 Supplement
VEGAPULS 42 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
1016153-EN-230316
Data
ISDU (dez) ISDU (hex) Size (Byte) Data type
Access Value
VendorName
16
0x0010
32
String32
R
VEGA Grieshaber KG
VendorText
17
0x0011
32
String32
R
www.vega.com
ProductName
18
0x0012
32
String32
R
VEGAPULS
ProductID
19
0x0013
32
String32
R
VEGAPULS 42
ProductText
20
0x0014
32
String32
R
Level sensor
SerialNumber
21
0x0015
16
String16
R
-
HardwareRevision
22
0x0016
20
String20
R
-
SoftwareRevision
23
0x0017
20
String20
R
-
Application-
SpecificTag
24
0x0018
32
String32
R/W
Sensor
FunctionTag
25
0x0019
32
String32
R/W
-
LocationTag
26
0x001A
32
String32
R/W
-
DeviceStatus
36
0x0024
1
U8
R
-
DetailedDeviceS-
tatus
37
0x0025
12
U8[12]
R
-
PDin
40
0x0028
6
-
R
See process data word
Teach Select
58
0x003A
1
U8
W
1 = Channel 1
2 = Channel 2
Teach Result State
59
0x003B
1
U8
R
0 = Idle
1 = SP1 success
2 = SP2 success
4 = Wait for command
5 = Busy
7 = Error
SSC1.1 Param
60
0x003C
8
Float[2]
R/W
see IO-Link Profile
Smart Sensors 2nd
Edition Version 1.1
September 2021
SSC1.1 Config
61
0x003D
6
Struct
R/W
SSC1.2 Param
62
0x003E
8
Float[2]
R/W
SSC1.2 Config
63
0x003F
6
Struct
R/W
MSDSC Descr
16512
0x4080
11
Struct
R
VEGA-specific device data
Data
ISDU
(dez)
ISDU
(hex)
Size
(Byte)
Data type Access
Value range
Measurement loop name
(TAG)
261
0x0105
19
String19
R/W
-
Device Revision
267
0x010B
2
U16
R
-
Unit of Lenght
268
0x010C
2
U16
R/W
1010 = m
1013 = mm
1018 = ft
1019 = in