13 Supplement
VEGAPULS 42 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
1016153-EN-230316
20 mA
≤ 3,6 mA
4 mA
t
2
3
4
1
Fig. 17: Run-up time and measured value output
1 U
B
On
2 Run-up time
3 Measured value output
4 U
B
Off
Output variable - three-wire 4 … 20 mA
Output signal
4 … 20 mA (active)
Connection technology
Three-wire
Range of the output signal
3.8 … 20.5 mA (default setting)
Signal resolution
5 µA
Fault signal, current output (adjustable)
Last valid measured value, ≥ 21 mA, ≤ 3.6 mA (Default)
Max. output current
21.5 mA
Load
See load resistance under Power supply
Output variable - Three-wire 1 x transistor
Output signal
Transistor PNP or NPN can be configured
Connection technology
Three-wire
Load current
max. 250 mA
Overload resistance
yes
Short-circuit resistance
Permanently
Voltage loss
< 3 V
Inverse current PNP
< 10 µA
Inverse current NPN
< 25 µA
Output variable - Three-wire 2 x transistor
Output signal
Transistor PNP or NPN can be configured
Connection technology
Three-wire
Load current
max. 250 mA
Overload resistance
yes
Short-circuit resistance
Permanently
Voltage loss
< 3 V
Inverse current PNP
< 10 µA
Inverse current NPN
< 25 µA