46
13 Supplement
VEGAPULS 42 • Three-wire with IO-Link (2 x transistor or 4 … 20 mA plus 1 x transistor)
1016153-EN-230316
Byte
Parameter
HexCode
Remark, value
4
M-SequenceCapability
0x2B
Frametypes, SIO-Mode, ISDU
5
Revision ID
0x11
IO-Link Revision 1.1
6
Input process data length
-
6 Byte
7
Output process data length
-
0 Byte
8, 9
VendorID
0x00, 0x62
98
10, 11,
12
DeviceID
0x00, 0x10, 0x00
4096
Process data word
Configuration
Bit
47 (MSB) …
16
15
…
2
1
0 (LSB)
Sensor
Measured value in m (0 … 15 m)
free
Out2
Out1
Formats
Value
Type
Out1
1 Bit
Boolean
Out2
1 Bit
Boolean
Measured value
32 Bit
Float
Events
HexCode
Type
6202
0x183A
FunctionCheck
6203
0x183B
Maintenance
6204
0x183C
OutOfSpec
6205
0x183D
Failure
Device data ISDU
Device data can be parameters, identification data and diagnostic information. They are exchanged
acyclically and on request of the IO-Link master. Device data can be written to the sensor (write) or
read from the device (read). The ISDU (Indexed Service Data Unit) determines, among other things,
whether the data is read or written.
IO-Link specific device data
Data
ISDU (dez) ISDU (hex) Size (Byte) Data type
Access Value
DeviceAccess
12
0x000C
2
U16
R
-
Profile Identification
13
0x000D
2
U16
R
0x0018
0x4000
PD-Descriptor
14
0x000E
12
U8[12]
R
-