40
6 Set up with the display and adjustment module
VEGADIS 82 • 4 … 20 mA/HART
45300-EN-170724
False signal suppression:
Deletes a previously created false signal
suppression. The false signal suppression created at the factory
remains active.
Peak values distance:
Resetting the measured min. and max.
distances to the actual measured value.
The following table shows the default values of the instrument. De-
pending on the instrument version, not all menu items are available or
some may be differently assigned:
Menu
Menu item
Default value
Setup
Measurement
loop name
Sensor
Medium
Liquid/Water
Application
Storage tank
Vessel form
Vessel bottom, dished form
Vessel top, dished form
Vessel height/
Measuring range
Recommended measuring range, see
"
Technical data
" in the supplement
Min. adjustment
Recommended measuring range, see
"
Technical data
" in the supplement
Max. adjustment
0,000 m(d)
Damping
0.0 s
Current output
mode
4 … 20 mA, < 3.6 mA
Current output -
Min./Max.
Min. current 3.8 mA, max. current
20.5 mA
Lock adjustment
Released
Additional settings Linearisation
curve
Linear
In this menu item, you can read out the instrument name and the
instrument serial number.
6.8 Parameter adjustment VEGAWELL 52
The main menu is divided into four areas with the following functions:
Basic adjustment:
Settings, for example of the unit of measurement,
position correction, adjustment, damping, signal output
Diagnosis:
Information, for example, on device status, peak value
Info - Instrument name
Main menu