56
10 Supplement
VEGADIS 82 • 4 … 20 mA/HART
45300-EN-170724
Torques
Max. torque for NPT cable glands and Conduit tubes
Ʋ Plastic housing
10 Nm (7.376 lbf ft)
Ʋ Aluminium/Stainless steel housing
50 Nm (36.88 lbf ft)
Signal and supply circuit
Operating voltage max.
35 V DC
Voltage drop with current value 4 … 20 mA
Ʋ Without lighting
max. 1.7 V
Ʋ With lighting
max. 3.2 V
Ʋ With activated HART resistance ad-
ditionally max.
4.5 V
HART resistance
200 Ω
Current range
3.5 … 22.5 mA
1)
Overcurrent resistance
100 mA
Reverse voltage protection
Available
Functional safety
SIL non-reactive
Current measurement (reference temperature 20 °C)
Measuring range loop current
3.5 … 22.5 mA
Deviation
±0.1 % of 20 mA
Temperature coefficient
±0.1 % of the span/10 K
Interval
250 ms
Display and adjustment module
Display element
Display with backlight
Measured value indication
Ʋ Number of digits
5
Ʋ Size of digits
W x H = 7 x 13 mm
Adjustment elements
Ʋ 4 keys
[OK]
,
[->]
,
[+]
,
[ESC]
Protection rating
Ʋ unassembled
IP 20
Ʋ mounted in the housing without lid
IP 40
Materials
Ʋ Housing
ABS
Ʋ Inspection window
Polyester foil
Functional safety
SIL non-reactive
1)
If the loop current is not sufficient for operation, the display does not work. When the measured values are
outside the measuring range, a message is displayed instead of the measured value.