I
nformation
:
T
o adjust with pressure
,
you simply enter the indicated actual
measured value
.
I
f the adjustment ranges are exceeded
,
the
message is displayed
"
O
utside parameter limits
"
.
T
he editing
procedure can be interrupted with
[
ESC
]
or the displayed limit
value can be accepted with
[
OK
]
.
T
he setup of
VEGABAR
53
for process pressure measure
-
ment is
fi
nished
.
A
ll other menu items are described in the
separate operating instructions manual of the indicating and
adjustment module
PLICSCOM
.
L
evel measurement
S
et up
VEGABAR
53
in the following sequence
:
1
S
elect application
"
L
evel measurement
"
2
S
elect adjustment unit
/
density unit
3
C
arry out position correction
4
C
arrying out min
.
adjustment
5
C
arrying out max
.
adjustment
I
n the menu item
"
A
pplication
"
you switch over from
"
P
rocess
pressure
"
to
"
L
evel measurement
"
.
I
n the menu item
"
U
nits of measurement
"
you select the
physical unit in which the adjustment should be carried out
,
e
.
g
.
mbar
,
bar
,
psi
...
T
he position correction compensates the in
fl
uence of the
mounting position or static pressure on the measurement
.
I
t
does not in
fl
uence the adjustment values
.
I
nformation
:
T
hese steps are not necessary for instruments which are
already preset acc
.
to customer speci
fi
cations
!
Y
ou can
fi
nd these data on the type label on the instrument and
in the menu items of the min
./
max
.
adjustment
.
PLICSCOM
enables the adjustment without
fi
lling or pressure
.
Y
ou can carry out the settings in the workshop without the
instrument having to be installed
.
A
lso the current measured value is shown in the menu items
for the min
./
max
.
adjustment
.
P
arameter adjust
-
ment
"
L
evel meas
-
urement
"
26
VEGABAR
53
-
P
ro
fi
bus
PA
S
etup with the indicating and adjustment module
PLICSCOM
28250
-
EN
-
051004