74
11 Supplement
SOLITRAC 31 • Profibus PA
43834-EN-211203
Ʋ Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB
PV
Ʋ 2. FB
Electronics temperature
Ʋ 3. FB
Pulse rate
Current value
10 mA, ±0.5 mA
Output variable - Level detection
Output
Ʋ Output signal
digital output signal, format according to IEEE-754
Ʋ Sensor address
126 (default setting)
Damping (63 % of the input variable)
0 … 999 s, adjustable
Profibus PA profile
3.02
Number of FBs with AI (function blocks
with analogue input)
3
Default values
Ʋ 1. FB
PV
Ʋ 2. FB
Electronics temperature
Ʋ 3. FB
Pulse rate
Current value
10 mA, ±0.5 mA
Relay output
Output
Relay output (SPDT), floating spdt
Switching voltage
max. 253 V AC/DC
With circuits > 150 V AC/DC, the relay contacts must be
in the same circuit.
Switching current
max. 3 A AC (cos phi > 0.9), 1 A DC
Switching current
Ʋ Standard
max. 3 A AC (cos phi > 0.9), 1 A DC
Ʋ USA, Canada
max. 3 A AC (cos phi > 0.9)
Breaking capacity
Ʋ Min.
50 mW
Ʋ Max.
Standard: 750 VA AC, 40 W DC (at U < 40 V DC)
USA, Canada: 750 VA AC
If inductive loads or stronger currents are switched
through, the gold plating on the relay contact surface will
be permanently damaged. The contact is then no longer
suitable for switching low-level signal circuits.
Contact material (relay contacts)
AgNi or AgSnO2 each with 3 µm gold plating