45
6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-211203
In this menu item you can adjust the SOLITRAC 31 to the isotope
installed in the source container.
For this purpose, check which isotope is in the source container. You
can find this information on the type label of the source container.
With this selection, the sensitivity of the sensor is adapted in an opti-
mum way to the isotope.
The SOLITRAC 31 requires this information for the decay compensa-
tion. An annual recalibration is hence not necessary.
Enter the requested parameters via the appropriate keys, save your
settings with
[OK]
and jump to the next menu item with the
[ESC]
and
the
[->]
key.
Enter here, the respective application.
This menu item enables adaptation of the sensor to the requested ap-
plication. You can choose between the following applications: "
Level
",
"
Point level
" or "
Summation Secondary
".
In this menu item you can activate the function of the current output.
When the output is activated, the instrument remains in its function as
a Secondary, but the 4 … 20 mA output of the SOLITRAC 31 can be
also used als single instrument.
When the output is active, the instrument has the complete function-
ality of a level measuring instrument. In this case, continue reading
under "
Parameter adjustment/Level measurement
".
Since the adjustment is very comprehensive, the menu points of
Function Blocks 1 (FB1) were put together in a submenu.
In menu item"
Channel
" you determine which measured value the
output refers to.
Isotope
Application
Outputs
AI FB1
Setup - AI FB1 - Channel