6 Set up with the display and adjustment module
SOLITRAC 31 • Profibus PA
43834-EN-211203
For this, the Secondary instruments must be defined as "Summation
Secondary". Select under the menu item "
Setup - Application
" the
function "Summation Secondary".
The address setting (MGC) on the Secondary instruments can be
freely selected. Only the address "99" is reserved for the Primary
instrument.
The Primary instrument must have the function "Level". For this pur-
pose, select under the menu item "
Setup - Application
" the function
"Level".
Set the address setting (MGC) on the Primary instrument to "99".
You have to enter the addresses of the Secondary instruments in the
list of the Primary instruments. This function is not possible in the sup-
ply and adjustment module. To do this you need PACTware with the
respective DTM.
The main menu is divided into five sections with the following func-
tions:
Setup:
Settings, e.g. for measurement loop name, isotope, applica-
tion, background radiation, adjustment, signal output
Display:
Settings, for example language, measured value display
Diagnosis:
Information, for example, of device status, peak value,
simulation
Additional adjustments:
Instrument unit, reset, date/time, copying
function
Info:
Instrument name, hardware and software version, date of manu-
facture, instrument features
Check if the correct language is already set for the display. If not,
you can change the language in the menu item "
Display - Menu
language
".
Start with the setup of SOLITRAC 31.
In the main menu item "
Setup
", the individual submenu items should
be selected one after the other and provided with the correct param-
eters to ensure optimum setting of the measurement. The procedure
is described in the following.
Main menu
Procedure