Smart-HS0101 / User Manual
25
Revision
№ 01
-
come. The data transfer period adjustable from 5 minutes to 24 hours. Data transferring in
random point in time during set period. At the next communication session, the device starts
sending accumulated packets with readings, from the earliest to the latest.
With the "Confirmed uplinks" option turned on, the device will send the next packet only
after receiving a confirmation of the delivery of the previous one. If such confirmation have not
received after the fulfilled in the settings uplink number of transmission, device completes the
communication session until the next one according to the schedule. In this case, the device
continues to collect data according to the data collection period and store it in memory. Non-
transmitted packets remain in the device memory until the next communication session.
With the "Confirmed uplinks" option turned off, the device just sends all accumulated
packets to the network in order from the earliest to the latest. There are no checks of package
delivery in this mode. There are no non-transmitted messages in the device memory.
Data collection period when measurements are out of specified temperature/humidity
range set independently and may change from 5 minutes to 24 hours.
Opening sensors settings
– allows to setting the alarm message sending option for
every Hall sensor, exactly by the close or open door (window) or in both of these cases. In
addition, you can switch off one or both Hall sensors. Inactive sensor means that there is no
alarm message sending and message have no alarm flag but sensors state will transmitting in
standard message.
Move alarm settings
– allows setting the internal accelerometer sensitivity on one of
the three levels: low, mid or high or to switch off the sensor. Inactive sensor means that there
is no alarm message sending and message have no alarm flag but vertical tint angle value will
transmitting in standard message.
Maximum alarm sending frequency may be equal to 1, 2, 3, 4, 5, 10, 15, 30 and 60
seconds.
Temperature and humidity thresholds settings
– allows specify range of values for
which alarm message will be sent.
Temperature thresholds may change from -40 °С to +85 °С in increments of 1 °С.
Humidity thresholds may change from 0% to 100% in increments of 1%.
«Send alarm when data out of thresholds». If that parameter active then immediately as
temperature/humidity value come out of specified range then will be form and transmit alarm
message. Every following message, which will form according to the data collection period,
will have sent according to the communication period.