Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
83
Function Code:
606
Version 1
Function Type:
Set Tank 20 Point Full, 95%, 90%,...Volumes
Command Format:
Inquire:
Display:
<SOH>S606TTGGGGGGgggggg...
<SOH>I606TT
or:
<SOH>S606TTGGGG,gggg,GGGG,...
Computer:
<SOH>s606TTFFFFFFFF...
<SOH>i606TT
Notes:
1.
TT - Tank Number (Decimal, 00 = all)
2.
GGGGGGgggggg - Series of 20 Volumes, Gallons (Decimal)
3.
FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I60601
22-05-01 15:07
TANK 20 POINT VOLUMES
TANK PRODUCT LABEL GALLONS
1 REGULAR UNLEADED 10000 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
<ETX>
Typical Response Message, Computer Format:
<SOH>i606TTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF...&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00 = all)
3.
FFFFFFFF - Series of 20 Volumes, Gallons (ASCII Hex IEEE float)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum