Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
75
Function Code:
575
Version 5
Function Type:
Set Dial Type
Command Format:
Inquire:
Display:
<SOH>S571RRDDDDDD
<SOH>I571RR
Computer:
<SOH>s571RRHHHHHHHH
<SOH>i571RR
Notes:
1.
DDDDDD - Site ID (Decimal)
Typical Response Message, Display Format:
<SOH>
I57500
JUL 8, 2009 9:02 AM
SITE ID
RCVR SITE ID
1 123456
<ETX>
Typical Response Message, Computer Format:
<SOH>i57500YYMMDDHHmmRRHHHHHHHH&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
RR - Receiver Number (Decimal)
3.
HHHHHHHH - Site ID (Hex)
4.
&& - Data Termination Flag
5.
CCCC - Message Checksum