Serial Interface Manual
•
TLS2 Monitoring Systems
Part No. 577013-767, Revision H
45
Function Code:
235
Version 5
Function Type:
In-Tank Mass/Density Delivery Report 2
Command Format:
Display:
<SOH>I235TT
Computer:
<SOH>I235TT
Typical Response Message, Display Format:
<SOH>
I235TT
04-30-09 2:46 PM
T 1:PRODUCT 1 TC TC
INCREASE DATE / TIME VOLUME MASS DENSITY OFFSET WATER TEMP HEIGHT
END: 06-08-09 1:40 PM 9199 58634 47.68 -0.022 1.96 77.54 20.78
START: 06-08-09 1:35 PM 7338 46618 47.52 -0.022 1.96 76.68 16.52
AMOUNT: 1860 12015
<ETX>
Typical Response Message, Computer Format:
<SOH>i235TTYYMMDDHHmmTTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf...
TTpddYYMMDDHHmmYYMMDDHHmmNNFFFFFFFFf&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
p - Product Code (single ASCII character [20h-7Eh])
4.
dd - Number of Deliveries to follow (Decimal, 00=no data)
5.
YYMMDDHHmm - Starting Date/Time
6.
YYMMDDHHmm - Ending Date/Time
7.
NN - Number of eight character Data Fields to follow (Hex)
8.
FFFFFFFF - ASCII Hex IEEE float:
1. Starting Volume
2. Starting Mass
3. Starting Density
4. Starting Water
5. Starting Temp
6. Ending Volume
7. Ending Mass
8. Ending Density
9. Ending Water
10. Ending Temp
11. Starting Height
12. Ending Height
13. Starting TC Density
14. Ending TC Density
15. Starting TC Volume
16. Ending TC Volume
17. Starting Total TC Density Offset
18. Ending Total TC Density Offset
9.
f - Default Density Flag (0=new value, 1=default)
10.
&& - Data Termination Flag
11.
CCCC - Message Checksum