Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485
TLS-IB Specifications
5-8
TLS-IB Specifications
PHYSICAL SPECIFICATIONS
• Width w/door closed: 188 mm (7.6”) - Width w/door open: 235 mm (9.6”)
• Height: 163 mm (6.7”)
• Depth w/door closed: 50 mm (2.6”), Depth w/door open: 228 mm (9”)
• Weight: 1.8 kg (3.5 lbs)
• The TLS-IB unit contains one CPU/Power Supply board (in unit)
• Removable plug type connections
• Conduit knockouts for intrinsically-safe wiring: 1/2”, 3/4”, and 1” I.P.S. (2 places)
ENVIRONMENTAL SPECIFICATIONS
• TLS-IB storage and operation: indoor, climate controlled
• Operating temperature range: 0 to +40 °C
• Storage temperature range: -40 to +74 °C
• LVD and EMC compliant
• UL/cUL approved and ATEX approved
ELECTRICAL SPECIFICATIONS
• TLS-IB operating voltage: 120/240 Vac, 2 A max
• Power Supply fuses F1 and F2 are
NOT
field replaceable. The rating for both fuses is 2 A, Type T (Time Lag)
• Intrinsically-safe circuit for scanning Mag Probes
SOFTWARE SPECIFICATIONS
• System software upgradeable by a PC program
• RAM clear jumper (Figure 5-2 on page 5-3)
• Factory boot-up mode for self testing
• Supports tank volume reports.
• Supports Density and Density Offset
SERIAL COMMUNICATIONS INTERFACE (SCI)
• RS-232 or RS-485
• Baud rate options: 300, 600, 1200, 2400, 4800, 9600; default 2400
• Parity options: None, Odd, Even; default Even
• Data length options: 8 or 7; default 7
• Number of stop bits options: 1 or 2; default 1