Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & RS-485
TLS-IB Specifications
5-11
RESPONSE MESSAGE FORMAT FOR FUNCTION CODE 64C
The
Set Field Density And Temperature
(64C)
Function Code is applicable to TLS-IB Form Numbers 846620-
580, 846660-580 and 846690-580 only.
Function Code:
64C
Function Type:
Set Field Density/Temperature Measurement
Command Format:
Display:
<SOH>S64CTTDD.tttTTT.hh<SOH>I64CTT
or:
<SOH>S64CTTDD.t,TT.h
Computer:
<SOH>s64CTTddddddddtttttttt<SOH>i64CTT
Notes:
1.
TT - Tank Number (Decimal, 00=all for inquiry only)
2. DD.ttt - Field Density Measurement (Decimal)
3. TTT.hh - Field Temperature Measurement (Decimal)
4. dddddddd - Field Density Measurement (ASCII Hex IEEE float)
5.
tttttttt - Field Temperature Measurement (ASCII Hex IEEE float)
Typical Response Message, Display Format:
<SOH>
I64CTT
T 1
DATE / TIME DENSITY TEMP TC DENSITY TC REF TEMP TC OFFSET
TLS: 721.82 21.94 728.19 15.00 0.00
FIELD: 721.79 22.06 728.26 15.00 0.07
TOTAL:
<ETX>
Typical Response Message, Computer Format:
<SOH>i646TTYYMMDDHHmmTTNNYYMMDDHHmmnnFFFFFFFF...FFFFFFFF
YYMMDDHHmmnnFFFFFFFF...FFFFFFFF&&CCCC<ETX>
Notes:
1.
YYMMDDHHmm - Current Date and Time
2.
TT - Tank Number (Decimal, 00=all)
3.
NN - Number of Records to follow (Hex)
4.
YYMMDDHHmm - Date/Time
5.
nn - Number of eight character Data Fields to follow (Hex)
6.
FFFFFFFF - ASCII Hex IEEE float:
1. TLS Density
2. TLS Temp
7.
&& - Data Termination Flag
8.
CCCC - Message Checksum