Wiring/Miscellaneous For TLS-IB Consoles W/RS-232 & With & W/O IFSF)
TLS-IB Specifications
4-14
ENVIRONMENTAL SPECIFICATIONS
• TLS-IB storage and operation: indoor, climate controlled.
• Operating temperature range: 0 to +40 °C.
• Storage temperature range: -40 to +74 °C.
• LVD and EMC compliant.
• UL/cUL approved and ATEX approved.
ELECTRICAL SPECIFICATIONS
• TLS-IB operating voltage: 120/240 Vac, 2 A max.
• The Power Supply board fuses F1 and F2 are
NOT
field replaceable. The rating for both fuses is 2 A, Type T
(Time Lag).
• Intrinsically-safe circuit for scanning Mag Probes.
SOFTWARE SPECIFICATIONS
• Two system interface modes: Serial and IFSF interface.
• System, test, and alarm messages are transmitted through both the IFSF and the Serial interfaces.
• System setup information is stored in EEPROM.
• System software is contained in a snap-in PROM integrated circuit.
• RAM clear jumper.
• Factory boot-up mode for self testing.
• Optional tank volume reports.
IFSF INTERFACE
• International forecourt Standards Forum - The protocol for tank level gauge applications, Part III.3.
• System hardware includes: 3150 Neuron, FTT-10 Free Topology Transceiver, 32K PROM, 32K SRAM, dip-
switch selectable node address.
• Neuron controller software is contained in a PROM integrated circuit.
OPTIONAL RS-232 SERIAL INTERFACE
• Baud rate options: 300, 600, 1200, 2400, 4800, 9600; default 2400.
• Parity options: None, Odd, Even; default Even.
• Data length options: 8 or 7; default 7.
• Number of stop bits options: 1 or 2; default 1.
• No RS-232 hardware handshaking options; RX, TX, and Signal Ground. The TLS-IB serial interface connections
to J7 (on TLS-IB Power Supply Board, see Figure 4-3 on page 4-5)
are