TLS Console Setup for MAG-XL Flex Probe
Height Reading Adjustment
27
Figure 17. In-tank setup for TLS Consoles used with MAG-XL Flex Probes
972-14.eps
TLS Console Setup
Example of In-Tank Setup for MAG-XL Flex Probes used with TLS Consoles
Parameter
Value
Notes
PRODUCT LABEL T1:
Fuel Oil
Customer to specify product name
PRODUCT CODE:
1
Code used by the point-of-sale terminal
THERMAL COEFF:
0.00047
Coefficient value depends on product type
TANK DIAMETER:
432
Enter the internal tank height not diameter
1
TANK PROFILE:
LINEAR
2
Setting for Vertical Tanks
FULL VOLUME:
115,925
Ex: 115,925 gallon tank capacity
1
METER DATA PRESENT:
NO
Not Used for MAG-XL Flex Probe Setup
CAL UPDATE:
IMMEDIATE Leave at the default setting
FLOAT SIZE:
4.0 IN.
Always set to 4" for MAG-XL Flex Probes
WATER WARNING:
2.0
Not Used for MAG-XL Flex Probe Setup
HIGH WATER LIMIT:
4.0
Not Used for MAG-XL Flex Probe Setup
MAX or LABEL VOL:
110,000
Maximum safe working volume
OVERFILL LIMIT:
90%
Maximum volume warning during a delivery
HIGH PRODUCT:
95%
Maximum volume alarm setting
DELIVERY LIMIT:
20%
10%
Low tank volume warning
LOW PRODUCT:
Set to a level higher than the discharge port
LEAK ALARM LIMIT:
0
Not Used for MAG-XL Flex Probe Setup
SUDDEN LOSS LIMIT:
0
Not Used for MAG-XL Flex Probe Setup
TANK TILT:
0
2
Not Used for Mag-XL Probe Setup
PROBE OFFSET:
4
2
Distance between probe and tank bottom
1
T1: SIPHON MANIFOLDED
0
Not Used for MAG-XL Flex Probe Setup
T1: LINE MANIFOLDED
0
Not Used for MAG-XL Flex Probe Setup
Multiple Leak Testing Parameters
Not Used
Not Used for MAG-XL Flex Probe Setup
DELIVERY DELAY:
01
Delay time in minutes (up to 99)
PUMP THRESHOLD:
Not Used
Not Used for MAG-XL Flex Probe Setup
Press STEP to set additional tanks
Repeat above in-tank setup for each probe
Values shown above are for reference only
1
For f
u
rther det
a
il
s
on how to c
a
lc
u
l
a
te thi
s
v
a
l
u
e, reference the
a
ppropri
a
te
expl
a
n
a
tion
s
incl
u
ded in thi
s
m
a
n
ua
l.
2
S
etting thi
s
v
a
l
u
e correctly i
s
critic
a
l to prod
u
ct perform
a
nce.
S
ee TL
S
Limit C
a
lc
u
l
a
tion
s
on next p
a
ge.
3
3
3
3
3
3