MAG-XL Flex Probe Installation
Installing the TLS XL-Transmitter
21
transmitter. Push the end of the probe cable through the probe cable cord grip bushing and into the transmit-
ter. Pull the excess cable through the cord grip bushing as you lower the transmitter down onto the 1/2” hex
brass adapter. Screw the transmitter into the top of the 1/2” brass hex adapter until tight.
5.
Proceed to “Connecting MAG-XL Flex Probe Wiring” on page 23.
TLS XL-TRANSMITTER INSTALLATION - TOP OF TANK 2-INCH PIPE FITTING (ref. Figure 14
)
1.
Make sure the battery/dc power cable is not connected to the battery pack or dc power source at this time.
WARNING! To prevent ignition of flammable or combustible atmosphere the battery cable must
be disconnected from the battery pack.
2.
Get the pre-assembled junction box/conduit assembly. Remove the cover of the junction box. Feed the probe
cable into the bottom threaded opening of the junction box/conduit and screw the junction box/conduit onto
the probe’s threaded fitting in the top of the riser cap until tight. Coil up the probe cable and hang it out of the
way. Replace the cover on the junction box and screw it on tight.
3.
Feed the end of the cable up through the reducing bushing, the 1/2” nipple and out the 1/2” brass hex adapt-
er. Coil up about 12 inches of cable in the junction box (for a service loop) and then replace and tighten the
cover on the junction box.
4.
Get the TLS XL-Transmitter. Looking at the cover of the transmitter, notice that one of the cord grips is la-
belled to receive the probe cable and the other to receive the battery pack/dc power cable. Remove the nut
from the probe cable cord grip and notice that the rubber bushing is marked with a white dot (the bushing for
the battery cable has a larger opening and is not marked). Using a T-10 Torx driver, remove the cover of the
transmitter. Push the end of the probe cable through the probe cable cord grip bushing and into the transmit-
ter. Pull the excess cable through the cord grip bushing as you lower the transmitter down onto the 1/2” hex
brass adapter. Screw the transmitter into the top of the 1/2” brass hex adapter until tight.
5.