MAG-XL Flex Probe Troubleshooting
Troubleshooting
32
Once installed, the MAG-XL Flex Probe must not contact any other object, such as: the bottom of the tank,
ladders, the side wall or piping.
Electrical noise or magnetic interference can cause reading errors. Also, physically inspect the probe tube for kinks
or bends as the surface of the tube must be smooth and straight. Contact Veeder-Root Technical Support for
assistance with these issues.