Connecting Probe/Sensor Wiring to Consoles
TLS-
3
50/ProMax/EMC Consoles
58
TLS-350/ProMax/EMC Consoles
MODULE/CONNECTOR POSITIONS AND LABELING
Modular consoles have three bays in which interface modules can be installed; Comm bay (left door) and Power
and Interstitially Safe bays (right door).
Figure 56. Console Interface Module Bays
Most consoles will be shipped with modules installed as ordered. If additional features are added at a later date,
modules will be field installed.
In all cases, the position of the modules, their respective connectors and the devices wired to the
connectors must be recorded to prevent improper replacement during installation or service. A circuit
directory for Power and I.S. bay Interface Modules is adhered to the back of the right-hand door for this
purpose
.
During programming, module positions and the devices wired to each module are identified and stored in memory.
If a connector is removed and reinstalled on a different module after programming, or if an entire module with its
connector is removed and reinstalled in a different module slot, the system will not properly recognize the data
being received.
Module Position
1.
Record on the circuit directory the type of module in each slot location.
2. If a system contains multiple modules of a single type (i.e., two Probe/Thermistor Interface Modules), they may
be swapped between their respective slot locations,
however,
the connectors must remain with their
original locations, not with the original modules
.
Connector Position
1.
Identify all connectors according to their slot location using the self-adhesive numbering labels furnished with
each module. Accurately record on the circuit directory the location of each device wired to the connector as
you attach wires to the module.
2. Once a device has been wired to certain terminals on a connector and the system has been programmed, the
wires from that device may not be relocated to other terminals without reprogramming the system.
console\350rjmods.eps
Intrinsically
Safe Bay
Permissible
Modules
(Limit 8
per console)
1
2
3
4
5
6
7
8
16
15
14
13
12
11
10
9
1 2 3 4
I.S. Bay
Slot Numbers
Power Bay
Slot Numbers
Comm Bay
Slot Numbers
Comm Cage*