Mag-FLEX Installation And Handling Procedure
Probe Installation Requirements
The instructions herein are intended as reference material only, the Gilbarco Veeder-Root
training modules contain comprehensive information and must be completed before any
installation work is attempted - contact Gilbarco Veeder-Root for details.
Installation requires a minimum of two people to allow correct handling of the probe. Please note that the flexible
and therefore fragile nature of the Mag-FLEX probe makes it more prone to mechanical shock. The probe must not
be unpacked until it has been brought to its place of installation and where possible unpacked at the Tank top. The
probe corrugated shaft is supplied in a 1 meter diameter coil this coil MUST not be reduced in size. The packaged
curve is the maximum bend possible to prevent damage.
Miscellaneous Requirements
TANK ENTRY
The tank entry point provided must have an internal thread of 1½” BSP - or 4” BSP when installing a low level
water float.
PROBE ASSEMBLY
The process connection, water float, product float, weight and magnet are shipped pre-assembled on the probe.
TOOLS AND MATERIALS
Before starting the installation you should have the following tools & materials:
• Mag-FLEX probe suitable for the tank height. See Mag-FLEX Probe Length Calculation on page 12.
• 2-Core probe cable run from TLS location to tank top. See Cable Specifications For I.S. Apparatus Cabling on
• Surge protector BA-350 Part number 903313 (wired install only), or V-R P/N 848100-002 for wired install or
V-R P/N 848100-001 for wireless install
• Non-sparking 55 mm Spanner for the process connection 55mm WAF (Width across Flat)
• Liquid sealing material for process connection, compatible with the tank material & product to be monitored
• Non-sparking Hexagon key (5mm) for the locking screw
• Non-sparking 30mm Spanner for the gland 30mm WAF (Width across Flat)
• Measuring tape to establish the correct position to lock the probe shaft into place