Operation of the terminal unit 

Switching ON 

The unit is switched on by pressing the POWER button. It will start up in comfort mode. 

Changing between COMFORT and ECONOMY 

Pressing the POWER button for less than 2 seconds toggles between ECONOMY and COMFORT modes. Economy mode 
may be disabled with 

UP06

.  

Switching OFF 

Pressing the POWER button for more than 2 seconds, will switch the unit off. OFF and current time will be displayed in 
the LCD for the deluxe unit. Current temperature and OFF is displayed for the basic unit. 

Standard display 

Standard display is enabled with parameter 

UP08

. This display mode is active if no UP/DOWN or OPTION key has 

been pressed during the previous 30 seconds.  The contents of the large and small digits may be chosen with 
parameters 

UP09

 to 

UP10

.  

Should Standard display be disabled, the selected loop setpoint will be displayed in the small digits, the associated 
input in the large digits and the output in the right hand scale.  

Changing of set points 

Change the set point with the UP/DOWN buttons. Changing of set points may be disabled with 

UP01

Change Automatic, Fan, Heat or Cool only mode 

Select fan only mode by pressing the OPTION key for less than 3 seconds. Repeatedly pressing the OPTION key will 
toggle these selections: Fan only

 Heat only 

 Cool only 

 Auto.  Any other selection than Auto will display the 

manual override sign. Manually override may be disabled with UP-02 
 
 

Accessing advanced settings 

Pressing the option button for more than three seconds will start the advanced setup menu. The basic version will only 

show heat/cool setup. The deluxe version will allow access to the time setting function. 
The large LCD digits display SEL. The advanced setup menu accesses these settings: Heat / Cool change, Clock setup, 
Time schedule. The menu may be left by pressing the POWER button or by not pressing a button for more than 5 

minutes.  

 

Heat / Cool / Fan only change. Pressing the OPTION button toggles Heating – Cooling – Fan only mode.  

Access to Heat/Cool change may be disabled with UP-03 

Clock Setup and Time Schedule (only available on Deluxe versions) 

 

Clock Setup. The current time is displayed in the small digits. Pressing the OPTION button will enter the clock 
setup. The minutes are blinking and may be changed with the UP/DOWN buttons. Pressing OPTION saves the 
minutes and steps to the hours. The hours are blinking. Pressing the OPTION button again will step to the 
weekday. DAY1-7 is displayed. Day 1 stands for the first working day (Monday) of a 5-day working week. 
(See schedule). Select the day according to current weekday. Pressing Option again saves the settings and 

moves back to the SELECT menu.  

 

Time Schedules: press the option button while Pro is displayed in the small digits. Pro1 is now shown in the 
large digits, while the number 1 is blinking. Select time program by using UP/DOWN buttons. There are a 
total of 4 time programs with each 4 switching times available. Enter the time program by pressing the 

OPTION button. 
1.

 

Activate or deactivate the time program. Choose ON or OFF with the UP/DOWN buttons 

2.

 

Select weekday(s) = d1-7, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 
The next steps define the switching mode and time. The bar indicator on the right side shows 

programming progress. There are four switch times for each program.  

3.

 

Select desired operation mode. (no, OFF, ECO, ON, UNI), press OPTION to continue 

ƒ

 

no = disables this switching time 

ƒ

 

OFF = switches unit Off, enables reset timer 

ƒ

 

ECO = sets operation mode to On and Economy, disables reset timer 

ƒ

 

ON = sets operation mode to On and Comfort, disables reset timer 

ƒ

 

UNI = Does not change operation mode, only disables reset timer 

4.

 

Select switching time 00:00 to 23:45 in 15-minute steps; press OPTION to continue. 

5.

 

Repeat steps 3 and 4 for each switching time.  

Access to time schedules may be disabled with UP-04 

 

 

Summary of Contents for TLR-D5P-U SeriesTLR-D5P-24

Page 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Page 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Page 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Page 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Page 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Page 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Page 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Page 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Page 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Page 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Page 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Page 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Page 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Page 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Page 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Reviews: