Vector TLR-D5P-U SeriesTLR-D5P-24 Engineering Manual Download Page 5

 

TLR-D5P-U Engineering Manual

 

 

Doc: 70-07-0100, V2.2, Date: 20090201 

©2008 Vector Controls 

Page 5 

Mechanical design and installation 

The unit consists of two parts: The base unit and the terminal.  

Installation base 

The housing of the TLR base unit is a compact enclosure. The controller may be mounted in any orientation by surface 
mounting on a wall or in a cabinet with two screws or on a 35mm DIN rail. 
When mounting note the following: 

 

The controller should not be freely accessible after mounting. A protective housing should be used, if mounted 
outside an electrical cabinet.  

 

Ensure adequate air circulation to dissipate heat generated during operation

 

Local installation regulations must be observed. 

Mounting location terminal 

 

On an easy accessible interior wall, approx. 1.5 m (4.5’) above the floor in an area of average temperature. 

 

Avoid exposure to direct sunlight or other heat sources, e.g. the area above radiators and heat emitting 
electrical equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used 

Installation terminal 

1.

 

Install the mounting plate straight to the wall or the flush mounting box. Make sure that the nipple with the 
front holding screw is facing to the ground. Make sure the screw heads do not stand out more than 5 mm of 
the surface of the mounting plate.  

2.

 

Connect the wires of the terminals to the communication wires according wiring diagram 

3.

 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

4.

 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make sure 
the connection cable does not get into the way. 

5.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to 
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the 
screw too much. 

Connection base to terminal 

 

Max. Distance: 200m (650ft) 

 

Normal cables maybe used for wiring in an EMC-save environment. In an impaired EMC environment use only 
shielded cables. The operating voltage must comply with the requirements for safety extra-low voltage (SELV) 
as per  
EN 60 730. 

 

One terminal may drive up to 8 base units. See wiring for parallel connections. Total wire distance should not 
exceed 200 m (650ft).  

 

Conductor resistance will influence external temperature reading. 450 

 will result in an increase of 1°C (2°F). 

Compensate using UP-08 if external temperature is used to control unit.  

Summary of Contents for TLR-D5P-U SeriesTLR-D5P-24

Page 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Page 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Page 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Page 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Page 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Page 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Page 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Page 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Page 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Page 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Page 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Page 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Page 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Page 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Page 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Reviews: