Control Functions 

The controller is designed to control package units with up to two heating or cooling stages and one support fan. The 
unit may be controlled to run in fan only mode or automatic. In automatic mode, the controller will change heating or 
cooling stages according to the temperature difference of room temperature and setpoint. The fan will run while there 
is a stage active. Selecting mold protection will let the fan run continuously while the operation mode is ON or 
ECONOMY. See below for control logic of 2- or 4-pipe systems. 

Control parameters: 

 

Economy set point shift X

SBY

: This function shifts the set point while the operation mode is Economy. The 

heating set point W

H

 is reduced and the cooling set point W

C

 increased by the value of the Economy set point 

shift X

SBY

.  

 

Minimum and Maximum Set Point Limits

: Limits the adjustable range of the loop set point. The limits for 

heating and cooling sequence may be chosen individually. 

 

Switching offset

 for cooling and heating determines the temperature difference required for the second 

stage to activate.  

 

Switching Hysteresis

 defines when a fan speed change is reversed. The aim is to avoid unnecessary 

switching of fan speeds and thus to increase the life span of fan and relays. 

 

Mold Protection.

 The fan will not stop when the setpoint is reached while this parameter is activated. This 

way the room will still be ventilated although there is no need to vary the temperature. The valve will still be 
controlled according to temperature need. Mold protection should not be used for fan-only systems! 

 

Reversing Valve:

 Enable the reversing valve where the compressor is used for heating and cooling. The 

reversing valve will activate either in heating or cooling mode depending on CP19.  Due to physical limitations 
of the controller, only one stage may be active if reversing valve is enabled. See Control Logic for further 
information.  

 

 
 
 
 
 
 
 
Legend: 
T Input 

Signal 

O

QH

 Offset 

Heating 

 

O

QC

 Offset 

Cooling 

 

X

DZ

 Dead 

zone 

X

SBY

 

Economy set point shift 

W

H

 

Set point Heating  

W

C

 

Set point Cooling 

Q

C

Binary Output Stage Cooling 

Q

H

 

Binary Output Stage Heating  

 

Control Logic TLR-D5P 

System type 

CP19 

DO1  

DO2 

DO3 

DO4 

DO5 

Heating with reversing valve 

1 or 2 

FAN 

Stage 1 

Stage 2 

Rev. Valve if CP19 = 1 

Frost 

Cooling with reversing valve 

1 or 2 

FAN 

Stage 1 

Stage 2 

Rev. Valve if CP19 = 2 

Frost 

2 pipe system heat or cool 

FAN 

Stage 1 

Stage 2 

 

Frost 

4 pipe system Heating 

FAN 

Stage 1 

Stage 2 

 

 

4 pipe system Cooling 

FAN 

 

 

Stage 1 

Stage 2 

 

ON

OFF


°C, F] 

Q

C2

 

O

SH

 

W

H

 

O

SC

 

X

DZ

 

W

X

H

 

Q

C1

 

Q

H2

 

Q

H1 

Summary of Contents for TLR-D5P-U SeriesTLR-D5P-24

Page 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Page 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Page 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Page 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Page 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Page 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Page 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Page 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Page 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Page 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Page 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Page 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Page 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Page 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Page 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...