Vector TLR-D5P-U SeriesTLR-D5P-24 Engineering Manual Download Page 6

 

TLR-D5P-U Engineering Manual

 

 

Doc: 70-07-0100, V2.2, Date: 20090201 

©2008 Vector Controls 

Page 6 

 Display and Operation 

 
The operation terminal uses an LCD display and four  
operation buttons.  
Legend: 

1.

 

4-digit display of current value, time,  

control parameter or setpoint 

2.

 

Unit of displayed value, °C, °F, % or none 

3.

 

Indication of fan speeds 

4.

 

4-digit display of current value, time, control 

 parameter or setpoint 

5.

 

Operation modes: 

Comfort mode, 

 Economy mode, 

OFF

 Energy Hold Off 

6.

 

Symbols:  

Heating Active 

Cooling Active 

Schedule Set 

Fan Active 

Manual Override 

Frost Protection 

 

 

 

 

 

 

7.

 

Buttons for operating the controller 

POWER button: Pressing the button less than 2 sec toggles economy and comfort mode. Pressing the 
button for more than 2 seconds switches the unit off.  

UP and DOWN buttons: change setpoints and parameters. 

  

OPTION button: used for changing fan speed and accessing advanced setup. Acts as Enter in 
parameter changing menu. 
 

8.

 

While the fan is in operation, the Fan symbol will be indicated and the active Fan speed is displayed in the 
vertical scale. Activation of heating or cooling coil is indicated by the blinking of the respective symbol in the 
lower left corner of the display. 

 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on UP05 the unit will 
remain switched off, switch on automatically or return to the operation mode it was in before the power failure.  
The deluxe version includes a real time clock with a 48h backup battery powered through a super capacitor. The time 
does not need to be re-entered after a power failure.  

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will 
be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection display 
will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09 

Operation Modes 

 

Comfort: The unit is in full operation mode. All the control functions are operating according to their setpoints. 

The unit displays occupied mode.  

 

Economy: The set point is shifted according to parameters CP-04. The heating parameter is shifted down and 

cooling parameter up. The unit displays unoccupied mode. Fan speeds are limited to maximum medium fan 

speed. Economy operation may be disabled with UP-06.  

 

Energy Hold Off (EHO): The unit is switched off. All outputs are off. The temperature will still be monitored in 

order to activate the unit in case of frost. (If frost protection is enabled). Off and current time is displayed.  

Activation of operation modes 

 

Via operation terminal 

 

Clock: (Deluxe version only) Operation modes may automatically be switched according to daytime and 
weekday. The clock symbol will be indicated if time programs are activated.  

 

Infrared Remote Controller: (Deluxe version only) use OPR-1 to control the unit remotely 

 

Via external contact (comfort/economy) 

Note: Time programs will not operate, if operation mode is set to OFF by remote control or if time is not set.  

2

 

3

 

4

 

7

 

1

 

6

 

5

 

Summary of Contents for TLR-D5P-U SeriesTLR-D5P-24

Page 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Page 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Page 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Page 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Page 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Page 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Page 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Page 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Page 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Page 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Page 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Page 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Page 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Page 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Page 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Reviews: