Switching Delays 

Delay switching off: 

Using this delay will prevent rapid switching of the compressor. After switching on, the compressor will only switch off 
after the delay switching off time is expired. The selectable range is 0…255 seconds. 

Delay switching on: 

Using this delay will prevent rapid switching of the compressor. After switching off, the compressor will only restart 
after the delay switching on time is expired. The selectable range is 0…255 seconds. 

Delay on heat / cool change:  

For 4-pipe systems only: This delay prevents rapid switching of heating and cooling. The selectable range is 0…255 
minutes. The switching on delay will be reset after a heat - cool change. This will allow a reversing valve to open 
before a compressor starts. Enough time will therefore be required for the delay-on parameter. 

Delay on reversing valve 

For systems with reversing valve, it is required to set the fan on delay long enough for the reversing valve to open / 
close. The reversing valve is activated together with the fan.  

Fan delay 

Once there is an output demand, the fan will activate first, wait the required start delay time and then activate the 
control output. This will ensure stable air for heating or cooling and for the reversing valve to run to the correct 
position before the compressors are started.  
The control output will be switched off when the setpoint is reached. The fan keeps running until stop delay has 
expired. This delay prevents overheating and condensation on the coils.  

Controls Output 

Fan Output 

Demand 

CP20 

CP21 

Time [s] 

Summary of Contents for TLR-D5P-U SeriesTLR-D5P-24

Page 1: ...oost and delayed switching on or off Features Temperature control for 2 or 4 pipe package units 2 stages fan supported heating or cooling with reversing valve Temperature control for 2 pipe package un...

Page 2: ...it only 24V OPR 1 40 50 0001 2xAAA bat Remote controller S Tn10 2 SD Tn10 12 2 SD Tn10 20 2 SDB Tn10 12 SDB Tn10 20 SRA Tn10 SOA Tn10 40 20 0001 40 20 0002 40 20 0003 40 20 0051 40 20 0004 40 20 0005...

Page 3: ...if external sensor is used Environment Operation Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing Transport Storage Climatic Conditions Temperat...

Page 4: ...startup currents may be a multiple of the rated current of the fan Verify with the fan supplier if unclear Do not connect directly motors larger than 1kW Connection diagram Connection terminals Power...

Page 5: ...t to the wall or the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Make sure the screw heads do not stand out more than 5 mm of the surface of the m...

Page 6: ...rsion includes a real time clock with a 48h backup battery powered through a super capacitor The time does not need to be re entered after a power failure Frost Protection The controller will enter fr...

Page 7: ...s is to avoid unnecessary heating or cooling of such rooms while they are not occupied Override reset function The override reset applies when the unit is manually switched on while in scheduled off m...

Page 8: ...etup Time schedule The menu may be left by pressing the POWER button or by not pressing a button for more than 5 minutes Heat Cool Fan only change Pressing the OPTION button toggles Heating Cooling Fa...

Page 9: ...t points for the temperature loop may be changed Set point range is 15 to 30 C Boost Pressing the boost button activates a 5 minute boost The output will be fully opened for the period of 5 minutes in...

Page 10: ...order to return to the parameter selection level 9 Press the POWER button again so as to leave the menu The unit will return to normal operation if no button is pressed for more than 5 minutes User P...

Page 11: ...d change is reversed The aim is to avoid unnecessary switching of fan speeds and thus to increase the life span of fan and relays Mold Protection The fan will not stop when the setpoint is reached whi...

Page 12: ...ing on delay will be reset after a heat cool change This will allow a reversing valve to open before a compressor starts Enough time will therefore be required for the delay on parameter Delay on reve...

Page 13: ...on detectors for offices Remote enable Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridden by using the terminal or time sche...

Page 14: ...display the firmware version can be found on the lower 7 segment display the current revision index or sub version Accessing the control parameters Warning Only experts should change these settings Th...

Page 15: ...n heating cooling set point XDZ 0 100 C 200 F 1 0 C 2 F CP 13 Delay on Heat Cool change over 0 255 min 5 min Input configuration Parameter Description Range Default CP 14 External input 0 No external...

Reviews: