TCY3-T0121R 

 

TCY3-T0121R Series Intelligent Compact Controller 

Features 

 

Temperature control for 2-pipe, 4-pipe HVAC 
systems.  

 

-H version: Humidity control with integrated 
humidity sensor 

 

Universal PID and binary control for any 
analog input/output signal and range  

 

4 independent PID sequences, 12 
independent binary sequences 

 

1 modulating output for DC 0...10V or 0…20 
mA actuators with 10 bit resolution.  

 

1 Input for DC 0…5V, 0…10V or 0…20 mA 
sensors with 10 bit resolution 

 

1 internal temperature sensor and 1 external 
sensor input 

 

Multiple functions on external input: auto 
changeover, remote control 

 

Monitoring of low and high limits on all inputs.  
Programmable reaction in case of alarm. 

 

Feedback function for internal sensors and 
set points. 

 

Special functions for dehumidifying, set point 
shift and VAV control 

 

Transformation of display value according to 
analog sensor range 

 

Password protected programmable user and 
control parameters 

 

Blue backlight  

 

Deluxe Version only: 

o

 

Power Cap protected real time clock with 24h 
power backup 

o

 

16 switching times, grouped in 4 time 
schedules.  

o

 

Infrared remote control 

Applications 

 

Air Only Systems: Constant or Variable Air Volume systems for single or dual duct systems with options of: 

o

 

up to two reheat stages 

o

 

supply air, extract air cascade control 

o

 

humidity control 

o

 

Control for variable speed fans 

 

 

Air/Water Systems:  

o

 

Fan Coil units for 2-pipe or 4-pipe systems with options of: 

ƒ

 

Humidity control 

ƒ

 

Pressure control  

o

 

radiator control, chilled ceiling 

 

 

Water Only Systems: Radiator, floor heating or chilled ceilings 

 

 

Individual room control for hotel rooms, meeting rooms, etc.  

General Description 

The TCY3 is a stand-alone electronic universal controller with two autonomous control loops. Each control loop may use up 
to 2 PID sequences and 6 binary sequences. The TCY3-T0121R features 1 NTC temperature sensor and 1 analog input, 2 
binary outputs and one analog output. The outputs need to be assigned to the control sequences by parameters. A 
detailed configuration is possible by following a simple setup routine. The TCY3 can be configured using the standard 
operation terminal. No special tool or software is required.  

Doc: 70-000002 V1.0, 20101115 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

 

Summary of Contents for TCY3-T0121R

Page 1: ...kup o 16 switching times grouped in 4 time schedules o Infrared remote control Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o u...

Page 2: ...0 10 0021 Standard 88mm x 88mm No humidity sensor Compact PI controller with 1 TI int or ext 1 AI 2 DO Relay 1 AO TCY3 T0121R D 40 10 0022 Deluxe TCY3 T0121R U 40 10 0023 Standard 2 x 4 TCY3 T0121R U...

Page 3: ...oltage mode AO1 DC 0 10 V or 0 20 mA 250 max 9 76 mV resp 0 019 mA 10 bit 10 mA Relays Outputs AC Voltage DC Voltage DO1 DO2 0 48 VAC 2 1 2 A max each output 0 30 VDC 2 1 2 A max each output Environme...

Page 4: ...ators with constant running time are recommended Observe power limits on binary devices Binary auxiliary devices E g pumps fans on off valves humidifiers etc Do not directly connect devices that excee...

Page 5: ...5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations be...

Page 6: ...fsets and heat cool settings Programming function Acts as Enter to select menu option or accept changed parameter value 10 DOWN buttons decrement set points and parameters select menu options Operatio...

Page 7: ...VAV this would mean the loop is now changed to CAV This is especially useful while tuning the VAV system Pressing the OPTION key to move back to the temperature loop will cancel manual override Manual...

Page 8: ...working day Monday of a 5 day working week See schedule Select the day according to current weekday Pressing Option again saves the settings and moves back to the SELECT menu Time Schedules press the...

Page 9: ...tton steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be ful...

Page 10: ...fied now Use UP and DOWN key to adjust the value 5 After you are done press OPTION or POWER in order to return to the parameter selection level 6 Press the POWER key again so as to leave the menu The...

Page 11: ...et point limits for heating and cooling sequence are defined individually Summer Winter Compensation Shift the set point either towards the set point minimum negative shift or the set point maximum po...

Page 12: ...rol The algorithm used reduces the swinging tendency of the control loop and improves a direct approach of the current value to the setpoint The ID part is defined by two parameters The time interval...

Page 13: ...is Defines the difference between switching on and switching off of a digital sequence A small hysteresis will increase the number of switching cycles and thus the wear on associated equipment Delayed...

Page 14: ...ng of your controller from a central location by switching a contact to GND Note all ground levels of involved controllers must be the same Choose if heat or cool is to be active when contact is open...

Page 15: ...mount of air the VAV box is set to deliver It may be adjusted through the maximum limit on the analog output OP03 As cooling requirements decrease airflow dwindles until it reaches its minimum setpoin...

Page 16: ...g coils with mold protection Output while demand on any output switch off delay 60s The output is ON if demand exists on any other output The output switches off with a fixed delay of 60s if there is...

Page 17: ...meters password 241 Warning Only experts should change these settings The parameters are grouped according to following control modules Module Description 1L Loop 1 Heat Cool Temperature Input 1 2L Lo...

Page 18: ...Heat Cool setting by demand OFF Manual 2 pipe ON Automatic 4 pipe ON OFF OFF PID Control Sequence Parameter Description Range Default 1L 09 P band heating XPH 0 100 2 0 C 4 0 F 1L 10 P band cooling X...

Page 19: ...Direct Reverse related to Heat Cool setting OFF not related ON related ON OFF OFF PID Control Sequence Parameter Description Range Default 2L 09 P band reverse XPH Acc input 10 2L 10 P band direct XPC...

Page 20: ...meter Description Range Default IP 16 Alarm 3 Alarm for lower limit of universal input of LP2 OFF Not active ON Active OFF ON OFF IP 17 Alarm 3 low limit of universal input Acc input 0 IP 18 Alarm 3 H...

Page 21: ...t 6 Feedback of floating output 0 6 1 OP 01 AO1 Configuration of output signal depending on OP00 If OP00 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 He...

Page 22: ...g on OP12 If OP12 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 Heating and Cooling 2 pipe system YH1 YC1 YR1 YD1 If OP12 4 manual override Choose Manual...

Page 23: ...gh signal alarm active 7 Any alarm active ALA1 ALA4 0 7 0 OP 21 DO1 Action in case of alarm OFF close output ON open output ON OFF OFF Digital Output 2 Parameter Description Range Default OP 22 DO2 Co...