background image

 

TCY3-T0121R Engineering Manual 

 

Doc: 70-000002 V1.0, 20101115 

© Vector Controls GmbH, Switzerland 

Page 13 

Subject to alteration 

Binary Control 

Each loop has three reverse- (heating) and three direct- (cooling) acting binary sequences. The offset to the setpoint is 
adjustable for each sequence. The switching hysteresis is adjustable per control loop.  

 
Action of stages: 

The stages may be activated according three different patterns:  

One at the time:  

Only one stage is active at the time. The lower stage will be switched off when the higher stage gets 
active. Example: fan speed control. 

Cumulative: 

Multiple stages are active at the same time: The lower stage stays activated when the higher stage 
switches on. Example: Electrical heating stages 

Binary coded: 

In the first step only the first stage is active; in the second step only the second stage. In the third 
step both stage 1 and stage 2 are switched on. This is used for heating stages. The size of the 
second heating stage should be doubled the size of the first heating stage. For example 100W for the 
first  stage and 200W for the second stage. With two outputs we could create the following steps: 1. 
Step 100W, 2. step 200W, 3. step 300W.  

 

Action 

Stage 1 

Stage 2 

Stage 3 

One at the time 

Q

1

 

Q

2

 

 

Cumulative Q

1

 

Q

1

+Q

2

 

 

Binary coded 

Q

1

 

Q

2

 

Q

1

+Q

2

 

 
 
 
 

 
Binary Control  
Legend

T, U 

Input Signal 

O

QH

 

Offset Heating, Direct 

 

O

QC

 

Offset Cooling, Reverse 

X

H

 Switching 

Hysteresis 

 

X

DZ 

Dead zone 

X

SBY 

Standby set point shift 

W

H

 

Set point Heating, Reverse  

W

C

 

Set point Cooling, Direct 

Q

C

, Q

D

  Binary Output Stage Cooling, Direct 

Q

H

, Q

R

  Binary Output Stage Heating, Reverse 

 
 
Switching Hysteresis

: Defines the difference between switching on and switching off of a digital sequence. A small 

hysteresis will increase the number of switching cycles and thus the wear on associated equipment. 

 

 
Delayed switching

. Cumulative Heating/ cooling stages will not switch simultaneously with stage 1, in case of a sudden 

demand or at power on. Stage 2 will not start earlier than 5 seconds after stage 1 has been initiated.  
 

Input Configuration 

General 

Alarms

: Each input features low and high limit alarms. Each alarm is defined with a limit, a hysteresis and an enable 

parameter. The limit specifies the input signal level required to trigger the alarm. The hysteresis defines the difference 
between input signal and limit required to return the alarm state to normal. Once an alarm is triggered it will be displayed 
as ALA1, ALA2, ALA3 and ALA4. Each alarm needs to be acknowledged by pressing the RIGHT key.  
ALA1 = Lower limit of the input signal of control loop 1 (temperature) has been reached 
ALA2 = Upper limit of the input signal of control loop 1 (temperature) has been reached 
ALA3 = Lower limit of the input signal of control loop 2 (universal) has been reached 
ALA4 = Upper limit of the input signal of control loop 2 (universal) has been reached 
 

 
Averaging function

: Averaging function is used to prevent unwanted fluctuation of sensor signals. The controller 

measures every second the signal inputs. The input signal is now built over a number of measured values. Select how 
many values should be used to calculate the averaging signal. Control speed will slow down when a large number of 
samples are used for an averaging signal. This should be taken into account when defining the control parameters.  

 
Compensation

: Adjust input values if required 

ON

OFF

T [°C, F] 

U [V, mA] 

 

Q

C2, 

Q

D2

 

W

O

SH

 

W

X

DZ

 

O

SC

 

X

H

 

Q

C1, 

Q

D1

 

Q

H2, 

Q

R2

 

 

Summary of Contents for TCY3-T0121R

Page 1: ...kup o 16 switching times grouped in 4 time schedules o Infrared remote control Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o u...

Page 2: ...0 10 0021 Standard 88mm x 88mm No humidity sensor Compact PI controller with 1 TI int or ext 1 AI 2 DO Relay 1 AO TCY3 T0121R D 40 10 0022 Deluxe TCY3 T0121R U 40 10 0023 Standard 2 x 4 TCY3 T0121R U...

Page 3: ...oltage mode AO1 DC 0 10 V or 0 20 mA 250 max 9 76 mV resp 0 019 mA 10 bit 10 mA Relays Outputs AC Voltage DC Voltage DO1 DO2 0 48 VAC 2 1 2 A max each output 0 30 VDC 2 1 2 A max each output Environme...

Page 4: ...ators with constant running time are recommended Observe power limits on binary devices Binary auxiliary devices E g pumps fans on off valves humidifiers etc Do not directly connect devices that excee...

Page 5: ...5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations be...

Page 6: ...fsets and heat cool settings Programming function Acts as Enter to select menu option or accept changed parameter value 10 DOWN buttons decrement set points and parameters select menu options Operatio...

Page 7: ...VAV this would mean the loop is now changed to CAV This is especially useful while tuning the VAV system Pressing the OPTION key to move back to the temperature loop will cancel manual override Manual...

Page 8: ...working day Monday of a 5 day working week See schedule Select the day according to current weekday Pressing Option again saves the settings and moves back to the SELECT menu Time Schedules press the...

Page 9: ...tton steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be ful...

Page 10: ...fied now Use UP and DOWN key to adjust the value 5 After you are done press OPTION or POWER in order to return to the parameter selection level 6 Press the POWER key again so as to leave the menu The...

Page 11: ...et point limits for heating and cooling sequence are defined individually Summer Winter Compensation Shift the set point either towards the set point minimum negative shift or the set point maximum po...

Page 12: ...rol The algorithm used reduces the swinging tendency of the control loop and improves a direct approach of the current value to the setpoint The ID part is defined by two parameters The time interval...

Page 13: ...is Defines the difference between switching on and switching off of a digital sequence A small hysteresis will increase the number of switching cycles and thus the wear on associated equipment Delayed...

Page 14: ...ng of your controller from a central location by switching a contact to GND Note all ground levels of involved controllers must be the same Choose if heat or cool is to be active when contact is open...

Page 15: ...mount of air the VAV box is set to deliver It may be adjusted through the maximum limit on the analog output OP03 As cooling requirements decrease airflow dwindles until it reaches its minimum setpoin...

Page 16: ...g coils with mold protection Output while demand on any output switch off delay 60s The output is ON if demand exists on any other output The output switches off with a fixed delay of 60s if there is...

Page 17: ...meters password 241 Warning Only experts should change these settings The parameters are grouped according to following control modules Module Description 1L Loop 1 Heat Cool Temperature Input 1 2L Lo...

Page 18: ...Heat Cool setting by demand OFF Manual 2 pipe ON Automatic 4 pipe ON OFF OFF PID Control Sequence Parameter Description Range Default 1L 09 P band heating XPH 0 100 2 0 C 4 0 F 1L 10 P band cooling X...

Page 19: ...Direct Reverse related to Heat Cool setting OFF not related ON related ON OFF OFF PID Control Sequence Parameter Description Range Default 2L 09 P band reverse XPH Acc input 10 2L 10 P band direct XPC...

Page 20: ...meter Description Range Default IP 16 Alarm 3 Alarm for lower limit of universal input of LP2 OFF Not active ON Active OFF ON OFF IP 17 Alarm 3 low limit of universal input Acc input 0 IP 18 Alarm 3 H...

Page 21: ...t 6 Feedback of floating output 0 6 1 OP 01 AO1 Configuration of output signal depending on OP00 If OP00 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 He...

Page 22: ...g on OP12 If OP12 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 Heating and Cooling 2 pipe system YH1 YC1 YR1 YD1 If OP12 4 manual override Choose Manual...

Page 23: ...gh signal alarm active 7 Any alarm active ALA1 ALA4 0 7 0 OP 21 DO1 Action in case of alarm OFF close output ON open output ON OFF OFF Digital Output 2 Parameter Description Range Default OP 22 DO2 Co...

Reviews: