background image

 

TCY3-T0121R Engineering Manual 

 

Doc: 70-000002 V1.0, 20101115 

© Vector Controls GmbH, Switzerland 

Page 14 

Subject to alteration 

Temperature Input 

Accuracy in Kelvin, 
Temperature Inp

0.2

ut 

0 50  100

T °C 

The TCY3 includes an NTC-based passive temperature sensor. A sensor 
of the same type can be connected as alternative control input or as 
input for additional functions. The accuracy of the temperature input is 
shown in the table to the right. Specified accuracy can only be 
guaranteed by using a manufacturer approved temperature sensor. For 
best results use Sxx-Tn10 sensors.  

0.5

1.0

Choose the active temperature input (intern or extern) of control loop 1 
with 

IP00

Additional functions of the external temperature input:  

Following additional functions are available, in case the external temperature input is not used as input for control loop 1.  
 

Toggle of Standby and 
Comfort operation modes 

Standby and Comfort modes are controlled through an external contact by connecting 
the external temperature input to ground  

Activation Delay:

 Defines the delay the binary contact has to be open before 

standby mode is activated. 
This function may be used together with key card switches for hotels or motion 
detectors for offices.  

Remote Enable 

Opening the external temperature input will force the unit into the OFF operation 
mode. The operation mode cannot be overridden by using the terminal or time 
schedules. Connecting the external temperature input to GND returns control of the 
operation mode to the terminal and time schedule. This function may be used as 
window contact to prevent loss of energy.  

Heat-cool changeover with 
external switch 

Control heat and cool setting of your controller from a central location by switching a 
contact to GND. Note: all ground levels of involved controllers must be the same. 
Choose if heat or cool is to be active when contact is open.  

Auto changeover with media 
temperature sensor 

The external input may be used to automatically determine heating or cooling mode. 
Connect a qualified passive sensor to the external input and measure the temperature 
of the supply media. Heating or cooling mode are activated once the supply 
temperature is above or below the respective limits. The limits may be defined in 
software. Standard is 16°C (60°F) for cooling and 28°C (82°F) for heating. 
 

Universal Input: 

The analog input signals may be configured with a jumper to 0-10V, 0-5V and 4-20 mA. The jumper is 
located on the front side of the power part. The drawing on the right indicates the jumper placement for each 
signal type. The factory setting is 0-10 VDC. Only place the jumper vertically.  
The range of the input signal can be specified in software by setting a minimum and a maximum limit. The 
limits are in percent of the full range. 
The display value of the input signal may be specified according to its measuring range. For example a 
pressure sensor has a 4-20 mA output and a pressure range of 0 – 200 Pa. It is possible to transform the 
input signal into a different dimension by setting the lower and upper measuring range limit according to the 
features of the sensor device. In our example the display will read 100 for a 12 mA signal. Range values 
below 100 will have a resolution of 0.5, below 50 of 0.2 and below 25 of 0.1.  

Humidity Input (-H Version) 

The TCY3-T0121R-H includes a capacitive-based humidity sensor with 3% accuracy. The sensor may be used as control 
input, as feedback or display input. It will replace the analog input on loop 2, if configured as control input.  

AI1 

0…10V 

0…20m

RT or c

o

n

tact 

   

 

Summary of Contents for TCY3-T0121R

Page 1: ...kup o 16 switching times grouped in 4 time schedules o Infrared remote control Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o u...

Page 2: ...0 10 0021 Standard 88mm x 88mm No humidity sensor Compact PI controller with 1 TI int or ext 1 AI 2 DO Relay 1 AO TCY3 T0121R D 40 10 0022 Deluxe TCY3 T0121R U 40 10 0023 Standard 2 x 4 TCY3 T0121R U...

Page 3: ...oltage mode AO1 DC 0 10 V or 0 20 mA 250 max 9 76 mV resp 0 019 mA 10 bit 10 mA Relays Outputs AC Voltage DC Voltage DO1 DO2 0 48 VAC 2 1 2 A max each output 0 30 VDC 2 1 2 A max each output Environme...

Page 4: ...ators with constant running time are recommended Observe power limits on binary devices Binary auxiliary devices E g pumps fans on off valves humidifiers etc Do not directly connect devices that excee...

Page 5: ...5 m 4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations be...

Page 6: ...fsets and heat cool settings Programming function Acts as Enter to select menu option or accept changed parameter value 10 DOWN buttons decrement set points and parameters select menu options Operatio...

Page 7: ...VAV this would mean the loop is now changed to CAV This is especially useful while tuning the VAV system Pressing the OPTION key to move back to the temperature loop will cancel manual override Manual...

Page 8: ...working day Monday of a 5 day working week See schedule Select the day according to current weekday Pressing Option again saves the settings and moves back to the SELECT menu Time Schedules press the...

Page 9: ...tton steps through low medium high and automatic fan speeds Automatic fan speed will not be activated in FAN ONLY mode Boost Pressing the boost button activates a 5 minute boost The output will be ful...

Page 10: ...fied now Use UP and DOWN key to adjust the value 5 After you are done press OPTION or POWER in order to return to the parameter selection level 6 Press the POWER key again so as to leave the menu The...

Page 11: ...et point limits for heating and cooling sequence are defined individually Summer Winter Compensation Shift the set point either towards the set point minimum negative shift or the set point maximum po...

Page 12: ...rol The algorithm used reduces the swinging tendency of the control loop and improves a direct approach of the current value to the setpoint The ID part is defined by two parameters The time interval...

Page 13: ...is Defines the difference between switching on and switching off of a digital sequence A small hysteresis will increase the number of switching cycles and thus the wear on associated equipment Delayed...

Page 14: ...ng of your controller from a central location by switching a contact to GND Note all ground levels of involved controllers must be the same Choose if heat or cool is to be active when contact is open...

Page 15: ...mount of air the VAV box is set to deliver It may be adjusted through the maximum limit on the analog output OP03 As cooling requirements decrease airflow dwindles until it reaches its minimum setpoin...

Page 16: ...g coils with mold protection Output while demand on any output switch off delay 60s The output is ON if demand exists on any other output The output switches off with a fixed delay of 60s if there is...

Page 17: ...meters password 241 Warning Only experts should change these settings The parameters are grouped according to following control modules Module Description 1L Loop 1 Heat Cool Temperature Input 1 2L Lo...

Page 18: ...Heat Cool setting by demand OFF Manual 2 pipe ON Automatic 4 pipe ON OFF OFF PID Control Sequence Parameter Description Range Default 1L 09 P band heating XPH 0 100 2 0 C 4 0 F 1L 10 P band cooling X...

Page 19: ...Direct Reverse related to Heat Cool setting OFF not related ON related ON OFF OFF PID Control Sequence Parameter Description Range Default 2L 09 P band reverse XPH Acc input 10 2L 10 P band direct XPC...

Page 20: ...meter Description Range Default IP 16 Alarm 3 Alarm for lower limit of universal input of LP2 OFF Not active ON Active OFF ON OFF IP 17 Alarm 3 low limit of universal input Acc input 0 IP 18 Alarm 3 H...

Page 21: ...t 6 Feedback of floating output 0 6 1 OP 01 AO1 Configuration of output signal depending on OP00 If OP00 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 He...

Page 22: ...g on OP12 If OP12 1 2 control loop 1 or 2 select sequence 0 Heating Reverse YH1 YR1 1 Cooling Direct YC1 YD1 2 Heating and Cooling 2 pipe system YH1 YC1 YR1 YD1 If OP12 4 manual override Choose Manual...

Page 23: ...gh signal alarm active 7 Any alarm active ALA1 ALA4 0 7 0 OP 21 DO1 Action in case of alarm OFF close output ON open output ON OFF OFF Digital Output 2 Parameter Description Range Default OP 22 DO2 Co...

Reviews: