TCY3-T0121R Operation
Display and Operation
The operation terminal uses an LCD display and four operation buttons.
2
Legend:
1.
4-digit display of current value, time, control parameter or set point
2.
Unit of displayed value, °C, °F, % or none
3.
Graphical display of output or input value with a resolution of 10%
4.
4-digit display of current value, time, control parameter or set point
5.
Operation modes:
Comfort mode,
Standby mode,
Energy Hold Off
6.
Symbols:
Heating Active
Cooling Active
Schedule Set
Direct Acting
Active
Reverse Acting
Active
Cascade
Override
7.
POWER button
: Standard function: Pressing the button less than 2 sec toggles standby and comfort mode.
Pressing the button for more than 2 seconds switches the unit off.
Programming function: ESC function, to return to previous level or ignore changed value
8.
UP buttons
: increment set points and parameters, select menu options
9.
OPTION button
: Standard function: If pressed less than 2 sec access for different control modes
If pressed for more than 2 sec starts operation level for advanced users. Change of time schedules, offsets and
heat – cool settings.
Programming function: Acts as Enter to select menu option or accept changed parameter value.
10.
DOWN buttons
: decrement set points and parameters, select menu options
Operation Modes
•
Comfort
: The unit is in full operation mode. All the control functions are operating according to their setpoints.
The unit displays occupied mode.
•
Standby
: The set points are shifted according to parameters
1L00
or
2L00
. The heating parameter is shifted
down and cooling parameter up. The unit displays unoccupied mode. Outputs are limited to
OP04
standby
maximum. For two stages heating or cooling the second stage will not operate while in standby mode. Standby
operation may be disabled with
UP06
.
•
Energy Hold-Off (EHO)
: The unit is turned off, and "Off" is displayed. However, the inputs are still monitored and
the alarm functions will operate normally.
Activation of operation modes
•
Via operation terminal
•
Clock (Deluxe version only)
: Operation modes may automatically be switched according to daytime and weekday.
The clock symbol will be indicated if time programs are activated.
•
Infrared Remote Controller (Deluxe version only)
: use OPR-1 to control the unit remotely
3
4
1
5
6
9
8
7
Doc: 70-000002 V1.0, 20101115
© Vector Controls GmbH, Switzerland
Page 6