12
PGK
Capacity PGK 400×200-4-2,0
Water temperature 6/12°C
Air flow
Press. drop
Inlet air
temp.
Inlet air
humidity
Outlet air
temp.
Output
Water flow
Water
press. drop
m³/h
Pa
°C
% RH
°C
kW
l/s
kPa
576
43
25
50
16.4
1,6
0.06
1.2
576
48
30
45
16.4
3,2
0.13
5
864
86
25
50
16.5
2,4
0.09
3
864
98
30
45
17.4
4,5
0.18
9
1152
140
25
50
16.6
3,2
0.13
5
1152
160
30
45
18.3
5,5
0.22
13
Capacity PGK 600×300-4-2,0
Water temperature 6/12°C
Air flow
Press. drop
Inlet air
temp.
Inlet air
humidity
Outlet air
temp.
Output
Water flow
Water
press. drop
m³/h
Pa
°C
% RH
°C
kW
l/s
kPa
1296
49
25
50
15.9
5,5
0.22
4
1296
49
30
45
17.8
8,1
0.32
9
1944
95
25
50
16.7
7,5
0.30
8
1944
95
30
45
19.0
11,0
0.44
15
2592
153
25
50
17.4
9,3
0.37
11
2592
153
30
45
19.8
13,6
0.54
23
Capacity PGK 500×250-4-2,0
Water temperature 6/12°C
Air flow
Press. drop
Inlet air
temp.
Inlet air
humidity
Outlet air
temp.
Output
Water flow
Water
press. drop
m³/h
Pa
°C
% RH
°C
kW
l/s
kPa
900
44
25
50
15
3,1
0.12
4
900
51
30
45
15.5
5,8
0.23
11
1350
89
25
50
15.6
4,5
0.18
7
1350
103
30
45
16.7
7,8
0.31
18
1800
146
25
50
16.2
5,6
0.22
10
1800
167
30
45
17.7
9,4
0.37
26
Capacity PGK 500×300-4-2,0
Water temperature 6/12°C
Air flow
Press. drop
Inlet air
temp.
Inlet air
humidity
Outlet air
temp.
Output
Water flow
Water
press. drop
m³/h
Pa
°C
% RH
°C
kW
l/s
kPa
1080
44
25
50
15
3,7
0.15
4
1080
51
30
45
15.5
6,9
0.27
12
1620
89
25
50
15.6
5,4
0.21
7
1620
103
30
45
16.7
9,3
0.37
20
2160
145
25
50
16.2
6,7
0.27
11
2160
167
30
45
17.7
11,3
0.45
28