INSTALLATION
Series 65
44/103
Edition 2019-10-11
980029EB
4.6.2
Power Failure Option
These settings define what the valve is doing in case the power fails.
Parameter
Description
Enable
‘True’ enables the power fail reaction, in case of ‘False’ there is no
reaction on a power fail
State
Current power fail state
Functionality
Defines the functionality in case of power fails. This can be “open” or
“close”.
Delay
After this delay the power failure reaction starts after the power failed
Parameter location:
CPA
Power Fail Option
4.6.3
Digital I/O
On the power connecter there are two digital inputs and two digital outputs available.
See chapter «Power and sensor connection» to get more information about the pinning.
Each of the four IO (2 inputs and 2 outputs) has following parameters:
Parameter
Description
Enable
‘True’ enables the input or output
State
Current state of the input or output
Functionality
Defines the functionality of the input or output
Inverted
‘True’ inverts the input or output. In case of an input, an inversion means
that a ‘0’ activate (State gets 1) the functionality and a ‘1’ means not
activated (State gets 0)
Parameter location:
CPA
Power Connector IO