background image

13

11.03

Vedolux 30

Illustrations may differ from the actual product 

Allowing for printing errors and errors on proofs

Problems.burning.firewood

The most common problems that occur when burning firewood are usually the result of the boiler failing to reach a high enough 
temperature so that the boiler never really gets going. Another common problem is that the heat is not transferred to the 
accumulator tanks even though the wood is burning well in the boiler.

Poor.combustion.

Damp wood.

A ceramic boiler requires a high combustion temperature. To achieve 

this, the wood must be dry, moisture content 12- 25%.

Incorrect handling.

Read the instructions.

The wood is not suitable for the 

boiler.

The firewood should be approx. 20 in. long, with a width allowing three 

blocks to fit the width of the grate.

Constant “topping up”

Constant “topping up” lowers the combustion temperature and re-

duces the boiler output.

Shaped wood, rectangular wood.

If uniform blocks of wood are stacked on each other, a sold mass of 

wood is created with limited surface area for the fire to act on. Arrange 

the wood so there are gaps between the blocks.

Fails to burn.

The wood is bent and/or not suitable for the boiler. This is not the same 

thing as the firewood burning to a different extent in different parts of the 

boiler, which is normal.

Not enough air.

Check that the air valve is open. The fresh air intake of the boiler room 

must have at least the same cross sectional area as the flue duct.

Damper too open.

If the damper is too open, the air will not be correctly distributed in the 

boiler. Start with the damper fully closed.

The chimney runs downwards from 

the boiler connection.

The turbulence created takes away some of the draught. Fill the lower 

part with sand or similar material.

No accumulator control.

A ceramic boiler is at its most efficient when the ceramic is hot. The 

temperature in the boiler therefore needs to be increased quickly before 

charging begins. The service life of the boiler is shortened if there is no 

control system. Add a control system.

Ceramic not correctly positioned.

If the boiler is new, check that the ceramic has not moved during 

transport. Also check the seal with the combustion chamber walls.

High.flue.gas.temperature.

Tar and soot in the pipes.

Incorrect combustion. Check the firewood, the draught, the air intake 

and the handling. Clean the boiler.

Bypass damper open.

Close the damper. The bypass damper must only be opened for adding 

wood.

Combustion tunnel in wrong 

position.

The combustion tunnel must be inserted fully.

Faulty flue gas thermometer.

The thermometer may have been damaged by cleaning or by long 

periods of up draught burning.

Tar.and.soot.in.the.pipes.

Incorrect combustion.

See the section about high flue gas temperature.

Heat.is.not.transferred.from.the.

boiler.to.the.accumulator.

Wrong connections.

Check.

Circulation pump in accumulation 

control.

Check that the pump is operational. Most pumps have a speed control – 

check that the speed is not too low.

Air.

Vent. Check the installation. If installation is carried out according to 

“Connection to accumulator system”, the system will not be sensitive to 

air problems.

Wrong connection of accumulator. See the points above.

Boiling.noises.

Low pressure head.

Check the pressure, which should be about 14.5 psi. The expansion 

vessel must be dimensioned for the volume and for the temperature 

variations that occur.

Fan.fails.to.start.

Main switch in position O.

Set the main switches to position I.

Forgotten to connect the instant 

connector.

Connect the instant connector.

Overheating protection triggered. Reset the overheating protection.

The.safety.valve.opens.when.the.

system.is.warm.

Expansion vessel too small.

See the section about the “Expansion system” on page 5.

Initial pressure in the expansion 

vessel too high/low.

Check the pressure in the vessel, see the section about the “Expansion 

system”.

Summary of Contents for Vedolux 30

Page 1: ...Installation operation and care Vedolux 30 2011 03 31 xxxxxx SMOKELESS...

Page 2: ...ust not do in order to prevent damage or disturbance to the component the burner the process or the surroundings General General 2 Notes 3 Function 4 Vedolux 30 Ceramic combustion chamber Flue cleanin...

Page 3: ...3 Vedolux 30 Illustrationsmaydifferfromtheactualproduct Allowingforprintingerrorsanderrorsonproofs To be completed when the Vedolux 30 is installed Serial number Installation date Installer Tel Other...

Page 4: ...firewood is added Flue cleaning All flue ducts in the boiler are cleaned from the same hatch at the front of the boiler The hatch is hinged and is opened with a single operation The flue ducts are ro...

Page 5: ...7 6 2 3 12 13 14 1 1 2 13 19 Weight empty filled with water 639 860 lb lb Volume 26gal Design pressure 22psi Test pressure 31psi Pressure drop water flow 0 14 gal s 0 145psi Design temperature 220 F M...

Page 6: ...dolux 30 has a suction fan minimizing the chimney require ments Clearance to combustibles 12 sides and rear 18 top and 36 front Flue pipe The boiler is supplied with an angled flue pipe a flue pipe ru...

Page 7: ...with the applicable regulations The boiler has a cooling coil which combined with a suitable thermal valve is used to prevent the boiler temperature exceeding 230 F if the water boils Follow the inst...

Page 8: ...trolled by the thermostat 21 When the firewood is burnt out and the flue gas temperature falls below the value set for the thermostat 21 the fan and charging pump stop running If the boiler temperatur...

Page 9: ...s to fell the tree in spring just after the leaves have come out then wait a few weeks before trimming and splitting the wood During these weeks the leaves wilt and draw out the moisture After another...

Page 10: ...ose the bypass damper Check that you can see flames in the inspection glass Adding wood To prevent smoke and flames entering the room when adding wood you must open the bypass damper before opening th...

Page 11: ...he flue gases One way of telling whether it is time for cleaning is to check the flue gas ther mostat It is a good idea to clean the boiler if the flue gas tempera ture is approx 80 F higher than the...

Page 12: ...system the static head If the difference is 16 4 ft the pressure is 7 3 psi if it is 32 8 ft the pressure is 14 5 psi The necessary pressure in the heating system depends on the height difference bet...

Page 13: ...cboilerisatitsmostefficientwhentheceramicishot The temperatureintheboilerthereforeneedstobeincreasedquicklybefore chargingbegins Theservicelifeoftheboilerisshortenedifthereisno controlsystem Addacontr...

Page 14: ...76 psi 1 5 29 50 05 Cleaning tool bracket 1 30 00 11 Glass fibre cord 10mm m 1 7 30 00 30 Ceramic fibre paper 1x25mm m 1 1 34 31 04 02 Grate front V 30 1 34 31 04 03 Grate rear V 30 1 9 71 05 06 Firew...

Page 15: ......

Page 16: ...4644 226358 291 94 Kristianstad www varmebaronen se Sweden info varmebaronen se V rmebaronen AB retains the right to change the specification of included components without prior notice as part of it...

Reviews: