Alarm - warning - information
R11
HIGH TEMP,PANEL!
Cause: High temperature of panel circuit board
Remedy: Check the cause.
Highest permitted ambient temperature is
≤
30°C.
R12
LOW WATERLEVEL,TANK!
Cause: Low water level in the boiler
Remedy: Check the reason, add water and vent the system.
R13
SEE MANUAL!
Cause: A guard, high, low or temperature has been released
without tripping the load-break switch.
Remedy: Check the reason.
Yellow indicator flashing - warning
Automatic reset when the cause has ceased.
Y1
PEC
Cause: Increasing PEC values.
Remedy: See R9, High earth current, PEC.
Y2
OVERTEMPERATURE
Cause: The boiler temperature is higher than the boiler
temperature value.
Remedy: Check that the boiler has sufficient flow and that all
necessary valves are open.
Check the setting for over temperature.
Y3
WATER LEVEL
Cause: Variations in the signal from the boiler's level sensor.
Remedy: Check the reason, add water and vent the system.
Green indicator flashing - information
Something is preventing power increase/decrease.
Automatic reset when the cause has ceased.
G1
TIME BLOCK
Cause: Delayed power connection after restart after
power cut.
G2
LOAD MONITOR
Cause: Load guard limits power increase/decrease.
G3
EXT ANALOG PWR LIM.
Cause: The boiler's power increase/decrease is limited
by an external setpoint or stage limit.
G4.
LIMITING SET TEMP
Cause: The boiler temperature is restricted by min or
max limit.