Värmebaronen EK 15E

1

5

2

1 2 3 4

GND

0-10V

0-10V signal of connected output

The connected output of the 

electric flow heater can be 

obtained as a 0-10Vdc signal, 
which corresponds to 0-100% 

of

 the installed output.

Outdoor temperature sensor and alternative 

heating, option

See "User level" rows 7, 8 and 9 and "Advanced 

service level" rows 6, 7 and 15.

The outdoor temperature sensor is 
fitted to an outside wall, at half 
the height of the façade, close 
to a corner, facing north / north 
west. The sensor must not 

be placed where it will be 
exposed to the morning sun or 

close to valves, windows or doors.

 

The sensor is connected in clamps 1-2, with at least 0.4 mm

2

 

cable up to 30 meters.
The temperature can be changed with an external potential-
free contact function; alternative temperature.

 

Connection to clamps 3-4.

4

1

5

2

3 4

3

8

Optional Room Unit

Further information is provided with the room unit.

2 3

4

1

4

Current Transformers - Load Guard

See "Service level" rows 3 and 4!

The current transformers need not 
be connected if the function is not to be 
used. The guard is not phase-sensitive.

 

The current transformers are placed 
on the wires from the fuses, which 
must be protected. Connection 
must be made with a high-
voltage insulated cable, with a 
minimum area of 0.75 mm

2

. A joint 

conductor is connected in terminal 4.

10

Electrical installation

Electrical installation shall be carried out in accordance 

with the applicable regulations, by an authorized 

electrical installer or by someone who is covered 

by the company's self-inspection programme!

 

The electric flow heater and heating system must 

be filled with water and vented before the flow heater 

is connected to the power supply.

 

Low-voltage cables may not be laid parallel to high-

voltage cables.

 

Cables and pipes must be laid so that it is possible 

to remove the front plate and open the top plate.

 

Do not drill into the electric flow heater's cover 

plates. Cuttings can damage the electric flow 

heater's electrical equipment!

Connection power supply 400V 3N~

Cable area 5 x 6 mm

2

 Cu, fuse 25 A

L1 L2 L3 N

N N CP X

X01

3 x 25 A

N

L1 L2 L3

2

1

Circulation pump 230V~

See "Advanced Service level" row 23.

 

Control for circulation pump, max load 2A.

L1 L2 L3 N

N N CP X

X01

1

3

Output limitation / Output control, 0-10V

See "Advanced service level" row 13 and "Service 

level"l row 5!

Controlled by an external 

voltage signal, 0-10Vdc. 
The control signal controls 

the output stages 

0-100% of installed output.

 

Installed output is the number of 

stages the electric flow heater is allowed to use.
The existing jumpers 3-4 are removed.

 

The control signal is connected to terminals 4-5.

GND

SIGNAL

1

5

2

1 2 3 4

7

1

5

2

1 2 3 4

7

Blockage

A potential-free contact is 
connected to clamps 3-4.
The existing jumper 3-4 
is removed.

Summary of Contents for EK 15 E

Page 1: ...Installation and maintenance EK 15 E Electric flow heater 7 stage 14 7 kW 1212_EK15E_191017_en pwr 1 14 1 15 dsp 1 05 p typ 4...

Page 2: ...sator setpoints UTK Alternative temperature Alternative temperature with room unit Optional Room Unit Over temperature protection Overheating protection Action in the event of a risk of freezing Frost...

Page 3: ...onthat is important for optimum operation Tells you what you should or should not do to avoid personal injury Tells you what you should or should not do to prevent a component the electric flow heater...

Page 4: ...the value is changed the indicator flashes The new value is only applied after confirming by pressing The old value is removed if the row is left with or User level Reading and modification of the mos...

Page 5: ...rent alarm codes according to a rolling schedule Once the cause of the alarm is resolved and is acknowledged with OK the red indicator stops flashing The display will return to its normal display Ackn...

Page 6: ...rve parallel displacement 5 30 adjustment 20 UTK function switched off see Advanced Service Level row 15 Curve higher value provides warmer temperatures for cold outdoor temperatures 20 60 adjustment...

Page 7: ...time to stabilize UTK function switched off see Advanced Service Level row 15 Alternative temperature 15 15 C Adjustment See Outdoor temperature sensor and alternative heating in Electrical installat...

Page 8: ...ut 2 1 4 2 6 3 8 4 10 5 12 6 14 7 kW Current 3 6 05 9 1 12 1 15 1 18 1 21 2 A 7 UTK function switched off see Advanced Service Level row 15 UTK min Limitation of the supply line temperature Adjustment...

Page 9: ...16 above At Absolute temperature the selected temperature should not exceed 10 C 10 Manual activation of rows 19 and 20 Adjustment 0 Off 1 Limited to 15 minutes 0 Manual activation test run of output...

Page 10: ...see Advanced Service Level line 14 For testing and service the connection delay and output connect disconnect can be temporarily sped up see Service level rows 1 and 2 The electric flow heater should...

Page 11: ...few more times The pressure in a heating system varies with the temperature Do not add water unnecessarily Draining If the heating system needs to be drained of water the electric flow heater must fi...

Page 12: ...ontain corrosion limiting additives Suitable water line quality Alkalinity 60 mg l to avoid corrosion Carbonic acid content 25 mg l increase the risk of corrosion Sulphate contents 100 mg l may accele...

Page 13: ...and must be laid so that water pockets cannot form The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure System principles The figure...

Page 14: ...conductor is connected in terminal 4 10 Electrical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by...

Page 15: ...er 14 Overheating protection 15 Contactor power group three 16 Heating element output group three 8 4 kW 17 Heating element for output group two 4 2 kW 18 Heating element for output group one 2 1 kW W...

Page 16: ...ain only when the temperature has dropped below the limit Selectable in Advanced Service level rows 16 and 7 Low boiler temperature Boiler temperature lower than 7 C The electric flow heater s tempera...

Page 17: ...ard during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Boiler temperature C k V C k V C k V 5 141 9 4 7 40 30 3 7 75 8 2 2 3 10...

Page 18: ...tage size 2 1 kW Current stage 3 A Ingress protection rating IP x1 Flow requirements recommended t 10 C min max t 25 5 C 0 35 0 2 0 7 litres sec litres sec Pressure drop Volume 3 6 litres Design press...

Page 19: ...panel 1 700414 Overlay 1 6 210206 Temperature sensor 1 11 440090 Capacitor 1 12 130010 Switch 1 120009 Knob for switch 1 700223 Shaft for switch 1 13 180023 Miniature circuit breaker 1 14 120025 Over...

Page 20: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: