background image

tr

ou
b

le

s

h

o

o

ting

17

Värmebaronen EK 15E

Troubleshooting

Intervention that requires tools must be performed by a qualified electrician!

Fault

Possible cause of fault

Action

Indicators and 

display off. 

The electric flow heater 

has no power.

Check the main fuses.

Switch off.

Set switch to position. Connection delay can restrict output staging.

Control fuse triggered.

Check where the short circuit is, take remedial action and then reset the fuse.

Malfunction of the control 
electronics.

Change the circuit board.

Group fuse is 

triggered.

Immersion heater faulty.

Check the insulation of the immersion heaters, which are accessible when 
the electric flow heater's lower front plate and insulation are removed.

 

Change the defective container with immersion heater. Check that the power 
cables are not against the electrical connections.

The electric 

flow heater 

does not step 

up power even 

though the 

temperature 

in the electric 

flow heater is 

lower than the 

set value.

The boiler electric flow 
heater has been restricted.

Check the "Number of output stages" adjustment.

The electric flow heater 
is controlled by external 
signal.

Check the voltage of the signal.

Outside temperature 
compensator connected.

Check the settings for the UTK function.

Temperature sensor 
defective.

Take control measurements of the temperature sensor.

 

The sensor must not be connected to the circuit board during resistance 
measurement.

 

When the boiler is energized, voltage is measured in the sensor's connection 
points at the PCB.

Boiler 
temperature

°C

V

°C

V

°C

V

5

141.9 4.7

40

30

3.7

75

8.2

2.3

10

111.6 4.6

45

24.6 3.6

80

6.9

2

15

88.3 4.5

50

20.2 3.3

85

5.8

1.8

20

70.3 4.4

55

16.7

3.1

90

5

1.7

25

56.3 4.2

60

13.9 2.9

95

4.2

1.5

30

45.4 4.1

65

11.6

2.7

100

3.7

1.3

35

36.8 3.9

70

9.7

2.5

Outdoor 
temperature

°C

V

°C

V

-40

88.7 4.5

0

8.8

2.3

-35

64.2 4.3

5

6.8

2.0

-30

47.0

4.1

10

5.4

1.7

-25

34.7 3.9

15

4.2

1.5

-20

25.9 3.6

20

3.4

1.3

-15

19.5 3.3

25

2.7

1.1

-10

14.8 3.0

30

2.2

0.9

-5

11.4

2.7

Uneven 

regulation, 

the electric 

flow heater 

steps up a 

few stages 

and is then 

immediately 

stepped down, 

etc.

Water flow through the electric flow heater is too low.

 

Check that circulation pumps and valves are working.
This is an easy way to get an idea of the level of flow through the electric flow heater:

 

1.  Limit the output stages of the electric flow heater so that the output is constant, e.g., 

to four output stages.

2.  Allow the electric flow heater's temperature to stabilise.
3.  Measure the temperature increase between the return and flow lines of the electric flow heater.
4.  Calculate the flow through the electric flow heater using the formula below.
5.  Check against the flow details whether the flow is adequate.
  q = P / (∆t x 1.16) 

 Q = water flow in m3 / h. (m3 / h x 1000 / 3600 = litre / second)

 

P = electric flow heater's delivered output in kW

 

∆ t = temperature difference between the electric flow heater's return 
and flow lines in °C.

 

1.16 = water's thermal absorption coefficient.

Summary of Contents for EK 15 E

Page 1: ...Installation and maintenance EK 15 E Electric flow heater 7 stage 14 7 kW 1212_EK15E_191017_en pwr 1 14 1 15 dsp 1 05 p typ 4...

Page 2: ...sator setpoints UTK Alternative temperature Alternative temperature with room unit Optional Room Unit Over temperature protection Overheating protection Action in the event of a risk of freezing Frost...

Page 3: ...onthat is important for optimum operation Tells you what you should or should not do to avoid personal injury Tells you what you should or should not do to prevent a component the electric flow heater...

Page 4: ...the value is changed the indicator flashes The new value is only applied after confirming by pressing The old value is removed if the row is left with or User level Reading and modification of the mos...

Page 5: ...rent alarm codes according to a rolling schedule Once the cause of the alarm is resolved and is acknowledged with OK the red indicator stops flashing The display will return to its normal display Ackn...

Page 6: ...rve parallel displacement 5 30 adjustment 20 UTK function switched off see Advanced Service Level row 15 Curve higher value provides warmer temperatures for cold outdoor temperatures 20 60 adjustment...

Page 7: ...time to stabilize UTK function switched off see Advanced Service Level row 15 Alternative temperature 15 15 C Adjustment See Outdoor temperature sensor and alternative heating in Electrical installat...

Page 8: ...ut 2 1 4 2 6 3 8 4 10 5 12 6 14 7 kW Current 3 6 05 9 1 12 1 15 1 18 1 21 2 A 7 UTK function switched off see Advanced Service Level row 15 UTK min Limitation of the supply line temperature Adjustment...

Page 9: ...16 above At Absolute temperature the selected temperature should not exceed 10 C 10 Manual activation of rows 19 and 20 Adjustment 0 Off 1 Limited to 15 minutes 0 Manual activation test run of output...

Page 10: ...see Advanced Service Level line 14 For testing and service the connection delay and output connect disconnect can be temporarily sped up see Service level rows 1 and 2 The electric flow heater should...

Page 11: ...few more times The pressure in a heating system varies with the temperature Do not add water unnecessarily Draining If the heating system needs to be drained of water the electric flow heater must fi...

Page 12: ...ontain corrosion limiting additives Suitable water line quality Alkalinity 60 mg l to avoid corrosion Carbonic acid content 25 mg l increase the risk of corrosion Sulphate contents 100 mg l may accele...

Page 13: ...and must be laid so that water pockets cannot form The opening pressure of the safety valve is determined by the component in the system that tolerates the lowest pressure System principles The figure...

Page 14: ...conductor is connected in terminal 4 10 Electrical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by...

Page 15: ...er 14 Overheating protection 15 Contactor power group three 16 Heating element output group three 8 4 kW 17 Heating element for output group two 4 2 kW 18 Heating element for output group one 2 1 kW W...

Page 16: ...ain only when the temperature has dropped below the limit Selectable in Advanced Service level rows 16 and 7 Low boiler temperature Boiler temperature lower than 7 C The electric flow heater s tempera...

Page 17: ...ard during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Boiler temperature C k V C k V C k V 5 141 9 4 7 40 30 3 7 75 8 2 2 3 10...

Page 18: ...tage size 2 1 kW Current stage 3 A Ingress protection rating IP x1 Flow requirements recommended t 10 C min max t 25 5 C 0 35 0 2 0 7 litres sec litres sec Pressure drop Volume 3 6 litres Design press...

Page 19: ...panel 1 700414 Overlay 1 6 210206 Temperature sensor 1 11 440090 Capacitor 1 12 130010 Switch 1 120009 Knob for switch 1 700223 Shaft for switch 1 13 180023 Miniature circuit breaker 1 14 120025 Over...

Page 20: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: