CPS-2C INSTALLATION
CPS-2C Section
B-19
Troubleshooting
SYMPTOM
CAUSE
REMEDY
Temperature probe
reads
LO
Temperature is below -58°F
(-50°C).
Probe is disconnected or
defective.
Check all connections. If
the problem persists, and
the temperature is within
normal range, replace the
probe.
Temperature probe
reads
HI
Temperature is above
140°F (60°C).
Probe is short circuited or
defective.
Check all connections. If
the problem persists, and
the temperature is within
normal range, replace the
probe.
Displays are blank
CPS-2C is not powered.
Flat cable between the
main and top boards of the
CPS-2C
is disconnected.
Make sure the control is
powered.
Make sure the fuse is
correct.
Make sure the flat cable is
connected.