CPS-2C INSTALLATION
CPS-2C Section
B-11
Connection Procedure
Detailed Wiring Diagrams
Typical Sensor Wiring for Probes
The inside temperature sensor should be located in the area which gives the
most accurate temperature reading to achieve optimum ventilation. The sensor
should also be connected to the CPS-2C with a shielded two-wire cable. It should
be located in an area protected from operating machinery, animal bites,
personnel or anything that could damage the sensor. See also “General
installation guidelines”.
FIGURE NO. 2 Typical Temperature Probe Wiring
PROBE
IN
T
1
IN
T
2
GN
A
X1344
CPS-2C
JP1
INT 1 STD
INT 1 4-20mA
J P1
1
1
1
SHIELD
Note: Jumper must be set to STD mode in order to use the temperature mode.
FIGURE NO. 3 Typical Static Pressure Probe Wiring
IN
T
1
IN
T
2
GN
A
X1344
CPS-2C
8VA
C
GN
D
STATIC PRESSURE
GE-SP1 (4-20mA)
GN
A
PR
B
8 VA C
or
12V DC
Input
Adaptor
IA-15
JP1
INT 1 STD
INT 1 4-20mA
JP1
SHIELD
Note: Jumper must be set to 4-20mA mode in order to use the static pressure mode.