Technical Manual: TM80030
THERMICA WATER TO AIR COOLER
Model range: THERMICA10-VV-MMM-LLL
Revision: 1.0
Date of release: 2022-12-16
25/55
www.vareximaging.com
3.10.
Default parameter settings
Check the if the correct parameter settings are applied for the application. See §5.6
The default settings of the most important parameters are listed below:
Parameter
Description of function
Default value
A6
Upper absolute alarm limit
35°C
C1
Setpoint
33°C
F66
Proportional range P controller
13°C
F69
Maximum speed fan
100% (10V)
Table 3: Default parameter setting
WARNING:
An incorrect setting of the control parameters can cause a wrong cooling behavior and
result in damages to the system.