VAMP 135
Over-, under-, residual voltage and
frequency relay
Operation and configuration
VAMP Ltd
24
VAMP 24h support phone : +358 (0)20 753 3264
VM135.EN008
5.9.
Analog output mA OUTPUT
Via the submenus of the mA OUTPUT menu the following
functions can be read and set:
•
Analog output reading / editing a forced value (AO)
•
Enabling / disabling of forced control of the analog output
(FORCE)
•
Choosing the coupling of analog output (Link)
•
Setting the coupling minimum value (Min)
•
Setting the coupling maximum value (Max)
•
Setting the analog output minimum value (AOmin)
•
Setting the analog output maximum value (AOmax)
Available couplings to analog output
•
U12, U23, U31, Uline
•
UL1, UL2, UL3
•
U
0
, U2/Un
•
f
•
DI, DO
5.10.
Disturbance recorder menu
RECORDER
Via the disturbance recorder menu the following functions can
be read and set:
•
Recording mode (Mode)
•
Sample rate (Rate)
•
Recording time (Time)
•
Pre trig time (PreTrig)
•
Scroll list of active links (Links)
•
Add a link to the recorder (AddLink)
•
Clear all links (ClrLink)
•
Manual trigger (MnlTrig)
•
Count of ready records (ReadyRec)