7
2.12
An extractor fan may only be used in the same room as this appliance, or
in any area from which ventilation for the appliance is taken, if it does not affect
the safe performance of the appliance. Note the spillage test requirements
detailed further on in this manual. If the fan is likely to affect the appliance, the
appliance must not be installed unless the fan is permanently disconnected.
2.13
A fan-powered flue system tends to depressurise the room containing the
appliance. Normally no additional ventilation should be required. In
exceptional circumstances, however the spillage check (See further on in this
guide) may indicate a need for further ventilation in order to ensure that there is
adequate air replacement. If necessary seek expert advice.
In the Republic of Ireland (IE), permanent ventilation must comply with the
rules currently in force.
(a) Appliance Dimensions
(b) Shelf & Corner Wall Clearances
(c) Opening Requirements
Figure 1